C6.1.6/0613-0915/E 42
Code
Description
Range
Factory Setting
ZXDE
ZXME
ZXLE
C23
Number of active compressor when probe error
0(0) - 1(1) - 2(2)
1
L2
N.V.
N.V.
C24
Minimum capacity for digital compressor
0 to PMA
20
L1
N.V.
N.V.
C25
Maximum capacity for digital compressor
PMi to 100
100
L1
N.V.
N.V.
C26
Time with DGS at PMA before starting another load
0 to 255 sec
0
L2
L2
N.V.
C27
Time with DGS at PMi before switching off another load
0 to 255 sec
0
L2
L2
N.V.
C28
R404A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C29
R507 Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C30
R134A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C31
R22 Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C32
R407C Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C33
R407A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C34
R407F Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C35
R448A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C36
R449A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C37
R410A Enable function
Disable (0-NO) - Enable (1-YES)
Disable
N.V.
N.V.
N.V.
C38
Compressor regulation control signal
Pressure (0-PRS) - temperature (1-TMP)
Pressure
L2
L2
L2
D01
Output delay at start up
0 to 255 sec
5
L2
L2
L2
D02
Compressor On time with faulty probe
0 to 255 min
5
L2
L2
L2
D03
Compressor Off time with faulty probe
0 to 255 min
3
L2
L2
L2
D04
Minimum time between two starts (same compressor)
0 to 15 min
4
L2
L2
L2
D05
Delay between compressor switch-off and start-up (same compressor)
1 to 900 sec
120
L2
L2
L2
D06
Delay between two different loads start-up
[0÷99.5] min res.10sec
10
N.V.
N.V.
N.V.
D07
Delay between two different loads switch-off
[0÷99.5] min res.10sec
10
N.V.
N.V.
N.V.
D08
Minimum time a stage stays switched On
[0÷99.5] min res.10sec
0
N.V.
N.V.
N.V.
D09
Maximum time a stage stays switched On
[0.00÷24.00] hour res.10min
0:00
N.V.
N.V.
N.V.
D10
don delay enabled also for the first request
no (0-NU) - YES (1-YES)
NO
N.V.
N.V.
N.V.
D11
doF delay enable also for the first switching off
no (0-NU) - YES (1-YES)
NO
N.V.
N.V.
N.V.