1. DSP self-check error, restart the drive and fault
should go away.
2. If problem persists, replace the drive.
DC Bus Voltage is below 380V. Check the AC power
supply and if the right voltage is supplied according to
the drive model.
The drive running condition is not stable. Check the
compressor load and makes sure it is OK. Restart the
drive again. If problem persist, replace the drive.
AC Input Current
Fold Back Timeout.
1. Check the line voltage if it is < 500VAC.
2. Check the compressor is operating with in
specified limits.
3. If problem persists, replace the drive.
INPUT OC
FOLDBACK
TIMEOUT
Modbus
Communication Lost
1. Check mod-bus communication cable connections.
2. Check the communication parameters are set right.
3. Power cycle the drive.
4. If problem persists, replace the drive.
Sensor 2
(Thermistor, DLT)
High Temp
1. Check the DLT/Scroll Thermistor connection.
2. Check the compressor is operating with in
specified limits.
Verify proper airflow over the heat-sink of the drive.
Remove any obstructions. Check that the compressor
is operating within specified limits. Check the
mounting screws on the drive, make sure they are
tight. If the problem, still persists replace the drive.
Verify proper airflow over the heat-sink of the drive.
Remove any obstructions. Check that the compressor
is operating within specified limits. Check the
mounting screws on the drive, make sure they are
tight. If the problem, still persists replace the drive.
Power Module
Temp. Fold Back
Timeout
Verify proper airflow over the heat-sink of the drive.
Remove any obstructions. Check that the compressor
is operating within specified limits. Check the
mounting screws on the drive, make sure they are
tight. If the problem, still persists replace the drive.
OVER TEMP
FOLDBACK
TIMEOUT
Sensor 1 (High
Pressure Switch
Open)
Condensing Pressure beyond limit, system issue.
Compressor Model
Configuration Error
Compressor model and configuration code do not
match
High Pressure
Sensor Type
Configuration Error
Pressure sensor and configuration code do not match
Sensor 2
(Thermistor, DLT)
Low Temp or Open
1. Check the DLT/Scroll Thermistor connection.
2. Check the resistance of the sensor to ensure
values are with in specified limits.
SENSOR 2
LOW TEMP
OR OPEN
Certain faults have a trip limit, see modbus map for
details
Auto Config
Communication
Fault Timeout
Baud rate or Parity of the system controller not
matching with drive. Check whether system controller
is working, then Power Cycle the drive.
Check if the compressor is operating within specified
limits. Check if the cables are not shorted. Shutdown
and restart the drive.