18
UL Cable Fuse Sizes (continued)
Input
voltage
Frame
size
VT/I
L
current
amps
VT/I
L
current
amps
Recom
mended
fuse
(Class
J,
T, CF
or CC)
(max
rating)
100
kAIC
Recom-
mended
miniature
inverse-
time
molded-
case
circuit
breaker
(max
rating)
10/14
kAIC
Recom-
mended
Type E CMC
(max rating)
65 kAIC
Recom-
mended
inverse-
time
molded-
case
circuit
breaker
(max
rating)
100
kAIC
(open type
only for
3-phase)
NEC
wire
size
line
and
motor
AWG
NEC
wire
size
ground
AWG
Term-
inal
size
line
and
motor
AWG
Term-
inal
size
ground
AWG
380 Vac
to 480
Vac
50/60
Hz
3-Phase
FR1
2.2
2.6
6 4
6.3
15 14
14 18-8
16-10
4.3
5.2
10 8
6.3
15 14
14 18-8
16-10
5.6
6.7
15 10
10
15 14
14 18-8
16-10
7.6
9.1
30 15
10
15 14
10 18-8
16-10
FR2
12
14.4
3
0 20
16
20 12
10 20-6
12-8
16
19.2
40 25
25
30 10
10 20-6
12-8
23
27.6
60 32
32
40 8
10 20-6
12-8
FR3
31
35.7
70 \
40
50 8
8 20-6
10-
8
FR4
38 43.7
70 \
50
70 6
8 20-2
8-6
46 52.9
80 \
58
80 4
8 20-2 8-6
525
Vac
to 600
Vac
50/60
Hz
3-Phase
FR2
FR3
FR4
Notes:
· Can be any UL listed types with the same ratings.
7.5
10
13.5
18
22
27
Output rating
Input rating UL application

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Copeland EVM Series and is the answer not in the manual?

Emerson Copeland EVM Series Specifications

General IconGeneral
BrandEmerson
ModelCopeland EVM Series
CategoryDC Drives
LanguageEnglish

Related product manuals