4.3 Suction line conguration
An adequately sized suction header providing equal distribution of returning
refrigerant and oil to each individual compressor must be used. The non-
symmetrical design as shown below is acceptable and does not create oil level
problems between the compressors.
Figure 1: Scrolls in parallel
Figure 2: Oil return Figure 3: Suction line conguration
Table 2: Model applicability
Compressor models approved
Low temperature Medium temperature
ZF09K* to ZF48K* ZB15K* to ZB114K* ZS21K* to ZS11M*
Alternative methods using the sight glass connections for oil equalisation connections have been shown to work on specic systems.
Notes are given below on some possible methods, but because of wide variations in system design and operating conditions, these
methods cannot be given general approval by Emerson Climate Technologies. The user has to verify operation in each system type.
4.2 Gas and oil equalization tube at sight glass position
Emerson Climate Technologies has conducted tests to prove the satisfactory operation of up to three compressors in parallel using
a gas and oil equalising tube. The conguration of suction line and equalization line should be as described below (see sections 4.3
and 4.4).
This method can be used for:
Two or three ZF, ZS, ZB refrigeration Scroll compressors
They must all be the same model, not uneven sizes
All voltages
Refrigerants R404A, R507, R22
Same operating envelope as single compressor with injection where required
Adequate liquid oodback protection must be provided
Any sequence of compressors is allowed