What to do if my Emerson Liebert Prop Fan Condensing Unit unit will not start?
- JJill OrtizAug 15, 2025
If your Emerson Air Conditioner unit won't start, there could be several reasons. First, check the voltage at the input terminal block to ensure there is power to the unit. If there is no voltage at control connections 1 & 2, verify that the control setting requires cooling. If voltage is present, the lockout relay may be energized; check for 24VAC at control connections 2 & 3. An open control voltage circuit breaker at the transformer in the evaporator module could also be the cause; locate any short circuits and reset the circuit breaker. Also, the control software delays the compressor from starting for 3 minutes after stopping. Finally, check the compressor high discharge pressure/lockout relay.