EasyManua.ls Logo

Emerson Liebert Prop Fan Condensing Unit - Table 18 Electrical Data-Quiet-Line Models (95°F;35°C) 60 Hz; Table 19 Electrical Data-Standard Sound and Ambient Models (95°F;35°C) 50 Hz; Table 20 Electrical Data-High Ambient Models (105°F;41°C) 50 Hz

Emerson Liebert Prop Fan Condensing Unit
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
23
Table 18 Electrical data—Quiet-Line models (95°F/35°C) 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
208/230-1 208/230-3 460-3 575-3
27 2
FLA 13.0
WSA 16.0
OPD 25
37 3
FLA 18.8 12.3 6.4 5.2
WSA 23.3 15.2 7.8 6.4
OPD 40 25 15 15
42 3.5
FLA 14.8 6.9 5.9
WSA 18.3 8.5 7.3
OPD 30 15 15
67 5
FLA 21.1 10.9 8.8
WSA 25.9 13.4 10.8
OPD 45 20 15
* FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in Quiet-Line versions.
Table 19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 200/230-3 380/415-3
13 1 FLA 9.9
19 1.5 FLA 10.9
26 2 FLA 12.7 4.9
36 3 FLA 18.4 7.0
41 3.5 FLA 15.3 8.5
66 5 FLA 24.1 13.2
95 8 FLA 20.3
* FLA = Full Load Amps
Table 20 Electrical data—High ambient models (105°F/41°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 200/230-3 380/415-3
13 1 FLA
19 1.5 FLA
26 2 FLA 14.8 6.0
36 3 FLA 20.5 13.1
41 3.5 FLA 19.8 9.6
66 5 FLA 24.2 13.2
95 8 FLA
* FLA = Full Load Amps

Table of Contents

Related product manuals