EasyManua.ls Logo

Emerson Liebert Prop Fan Condensing Unit - Checklist for Completed Installation

Emerson Liebert Prop Fan Condensing Unit
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
24
2.8 Checklist for Completed Installation
___ 1. All items unpacked and checked.
___ 2. Proper clearances for service access maintained around equipment.
___ 3. Equipment is level and mounting fasteners are tight.
___ 4. Piping completed to refrigerant loop.
___ 5. All piping connections are tight.
___ 6. Piping routed to prevent chafing and rub-through.
___ 7. Piping has been evacuated and refrigerant charge added (if required).
___ 8. Line voltage to power wiring matches equipment nameplate.
___ 9. Power wiring connections completed, including earth ground.
___ 10. Power line circuit breakers or fuses have proper ratings for equipment installed.
___ 11. Control wiring connections completed.
___ 12. All wiring connections are tight.
___ 13. Foreign materials have been removed from area: in and around all equipment installed
(shipping materials, construction materials, tools, etc.).
___ 14. Fans and blowers rotate freely and in the proper direction.
___ 15. Blank startup sheet has been sent with the evaporator unit and is ready to be completed by
the installer.
Table 21 Electrical data - Quiet-Line models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 200/230-3 380/415-3
13 1 FLA
19 1.5 FLA
26 2 FLA 12.3 4.8
36 3 FLA 18.0 6.9
41 3.5 FLA 17.3 8.4
66 5 FLA 22.5 12.4
95 8 FLA
* FLA = Full Load Amps

Table of Contents

Related product manuals