What to do if my Emerson Liebert InteleCool 2 is not cooling?
- Jjustin22Jul 31, 2025
If your Emerson Air Conditioner isn't cooling, one potential cause is a low refrigerant charge, which you can check with gauges. Another reason could be that the compressor contactor isn't pulling in. In that case, check the voltage at the contactor; if there's no voltage, refer to the wiring diagram to find the voltage loss and check the enthalpy sensor for full CCW or D setting. Finally, ensure the thermostat is outputting correctly; it should have voltage output to the Y terminal during cooling.