Maintenance
19
Table 4 Pressure information
Design
Pressures
psig (kPA)
Minimum
psig (kPa)
R-407C
Maximum
psig (kPa)
R-407C
Suction 35 (241) 90 (620)
Liquid (Approx.) PSIG (kPa)
95°F (35°C) Ambient 250-290 (1723-2000)
Maximum 360-380 (2480-2618)
High Pressure Cutout 400 (2756)
Based on indoor conditions of 80°F (26.7°C), 50% RH, with clean filter(s).