How to fix high rack temperature in Emerson Liebert CRV Air Conditioner?
- SSheila BrennanAug 22, 2025
If the rack temperature is too high, it might be due to dirty filters. Try replacing them. For air-cooled units, ensure that remote condenser fans are running. Also, verify that remote temperature sensors are correctly positioned. Water/glycol units: Check cooling water supply and cooling water temperature. Verify unit positioning/room configuration, unit air baffles set-up, and cold aisle containment seals (if applicable). Consider reducing the rack heat load or adding cooling units if there is insufficient room-cooling capacity.