S428 Quick Start Overlap Time: When iCOM is ready with the boot process, a time can be added to
continue the static quick start mode, giving the Liebert iCOM the chance to build calls meanwhile,
and seamlessly overtake control when S428 times out.
S429 Last Quick Start Duration—Informational only. Shows the time of the last quick start.
S430 Boot loader Variables: IMPORTANT: any change of quick start (EN to Disable, or DIS the
Enable) must be followed by executing Boot Loader Variables: Save and Reboot.
Figure 115 Service—Service Contact Menu
NOTE
Quick start is performed at each power cycle, no matter if the unit was in operation or in an Off
state before the power cycle. When the unit was in an Off state and quick start is finished, the
unit will stop again.