EasyManua.ls Logo

Emerson Liebert CRV - Unit Handling and Moving

Emerson Liebert CRV
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Inspection and Unpacking
Liebert
®
CRV
12
3.2 Handling
Figure 6 Liebert CRV center of gravity
Always keep the packaged Liebert CRV upright and never leave it outdoors.
Be aware of the center of gravity indicated on the package and in Table 3 below:
Table 3 Center of gravity
Model No. /Cooling Type
Unit
Width
Distance from lower right front corner, ± 2 in. (51m)
X, in. (mm) Y, in. (mm) Z, in. (mm)
CR019 (DX) 300mm (12") 21 (154) 6 (154) 34 (860)
CR020
(air-cooled or water-glycol)
600mm (24") 20 (508) 12 (305) 28 (711)
CR035
(air-cooled or water-glycol)
600mm (24") 20 (508) 12 (305) 32 (813)
CR040
(chilled water)
600mm (24") 21 (533) 12 (305) 32 (813)
The center of gravity on the Liebert CRV varies with the options and the model's size.
Table 4 Weights without packaging
Model
No.
Electrical
Data
Weight ± 5%, lb (kg)
Air-Cooled Water/Glycol-Cooled Chilled Water
CR019 208/3/60 507 (230)
CR020 208/3/60 739 (335)
CR020
460/3/60 739 (335) 772 (350)
208/3/60 739 (335) 772 (350)
CR035
460/3/60 805 (365) 849 (385)
208/3/60 805 (365) 849 (385)
CR040
460/3/60 728 (330)
208/3/60 728 (330)
Z
Y
X