Operation in Teamwork Mode
139 Liebert
®
CRV
Table 35 Teamwork Mode 1 or 3, definition of Serial, Parallel and Local
Mode A (C = SUPPLY / F = SUPPLY) Teamwork Mode 3
Cooling On-Off Local
Cooling Capacity Local
Low Supply Limit Control N/A
Fanspeed Parallel
Re-Heat during Dehum Local
Humidification Serial
Dehumidification Serial
Mode B (C = REMOTE / F = REMOTE) Teamwork Mode 1
Cooling On-Off Local
Cooling Capacity Parallel
Low Supply Limit Control Local
Fanspeed Parallel
Re-Heat during Dehum Local
Humidification Serial
Dehumidification Serial
Mode C (C = RETURN / F = RETURN) Teamwork Mode 1
Cooling On-Off Local
Cooling Capacity Parallel
Low Supply Limit Control N/A
Fanspeed Parallel
Re-Heat during Dehum Local
Humidification Serial
Dehumidification Serial
Mode D (C = SUPPLY / F = REMOTE) Teamwork Mode 3
Cooling On-Off Local
Cooling Capacity Local
Low Supply Limit Control N/A
Fanspeed Parallel
Re-Heat during Dehum Local
Humidification Serial
Dehumidification Serial
Mode E (C = SUPPLY / F = RETURN) Teamwork Mode 3
Cooling On-Off Local
Cooling Capacity Local
Low Supply Limit Control N/A
Fanspeed Parallel
Re-Heat during Dehum Local
Humidification Serial
Dehumidification Serial
Mode F (C = REMOTE / F = RETURN) Teamwork Mode 1
Cooling On-Off Local
Cooling Capacity Parallel
Low Supply Limit Control Local
Fanspeed Parallel
Re-Heat during Dehum Local
Humidification Serial
Dehumidification Serial