EasyManua.ls Logo

Emerson Liebert InteleCool 2 - Table 7 Technical Data, 60 Hz - Standard Ambient Condenser, Continued

Emerson Liebert InteleCool 2
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
22
Table 7 Technical data, 60 Hz - Standard ambient condenser, continued
Model ET048, ET348 ET060, ET360
Compressor Type Scroll Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
Total 47900 (14.0) 56900 (16.7)
Sensible 35400 (10.4) 38800 (11.4)
95°F
(35.0°C)
Total 45600 (13.4) 53800 (15.8)
Sensible 34600 (10.2) 37700 (11.1)
105°F
(40.6°C)
Total 43100 (12.6) 50700 (14.9)
Sensible 33800 (9.9) 36800 (10.8)
110°F
(43°C)**
Total 41800 (12.3) 48600 (14.2)
Sensible 33100 (9.7) 35800 (10.5)
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
Total 44500 (13.0) 52200 (15.3)
Sensible 35000 (10.3) 38200 (11.2)
95°F
(35.0°C)
Total 42300 (12.4) 49800 (14.6)
Sensible 34100 (10.0) 36900 (10.8)
105°F
(40.6°C)
Total 39900 (11.7) 47300 (13.9)
Sensible 33100 (9.7) 35700 (10.4)
110°F
(43°C)**
Total 38700 (11.3) 44700 (13.1)
Sensible 32600 (9.6) 34900 (10.2)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
3
/hr)
0.0 - IN WG (0.0 Pa) 2030 (3450) 2030 (3450)
0.1 - IN WG (25 Pa) 1910 (3240) 1910 (3240)
0.2 - IN WG (50 Pa) 1770 (3010) 1770 (3010)
0.3 - IN WG (75 Pa) 1650 (2800) 1650 (2800)
0.4 - IN WG (100 Pa) 1520 (2580) 1520 (2580)
0.5 - IN WG (125 Pa) 1390 (2360) 1390 (2360)
Evaporator Air Flow - Wet Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
3
/hr)
0.0 - IN WG (0.0 Pa) 1800 (3060) 1800 (3060)
0.1 - IN WG (25 Pa) 1680 (2850) 1680 (2850)
0.2 - IN WG (50 Pa) 1580 (2680) 1580 (2680)
0.3 - IN WG (75 Pa) 1470 (2500) 1470 (2500)
0.4 - IN WG (100 Pa) 1360 (2310) 1360 (2310)
0.5 - IN WG (125 Pa) 1250 (2120) 1250 (2120)
Evaporator
Motor Hp (kW) 0.50 (0.37) 0.50 (0.37)
Filter Sizes - Quantity, in. (cm)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
Drain Connection - ID, in. 3/4 3/4
Weight - w/o Economizer, Ib/kg 470 (213) 470 (213)
Weight - with Economizer, Ib (kg) 490 (222) 490 (222)
* Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air.
** For applications above 110°F (43°C) use high ambient option.