Liebert.CRV+ Series Air Cooled Precision Air Conditioner
User Manual
Original Instruction
Version V1.4
Revision date March 4, 2015
BOM 31012977
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Copyright © 2014 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
Address: Block B2, Nanshan I Park, No.1001 Xueyuan Road, Nanshan District, Shenzhen 518055, P.
R. China
Homepage: www.emersonnetworkpower.com.cn
E-mail: overseas.support@emerson.com

Table of Contents

Questions and Answers

  • C
    Christopher MartinezAug 18, 2025
    How to fix Emerson CR035 EC fan that won’t start?
    • Z
      Zachary SandersAug 18, 2025
      If the EC fan of your Emerson Air Conditioner won’t start, check that the fan MCB is closed and that the power voltage of each phase is normal. Also, check J15 on the micro-processing control board to determine if the control board is faulty. Inspect the alarm lamp on the fan power module to see if it is faulty. Finally, check L1, L2, and L3 of the fan against power failure, phase loss, and low voltage; verify that the analog output is within the required range of 0 ~ 10Vdc; check if the motor is clogged or too hot; and look for hall failure. Clear any faults, cut off the fan power to cool the motor if it's too hot before powering it on again and if hall failure occurs, the factory service is required.
  • M
    Matthew PriceAug 20, 2025
    What to do if Emerson Air Conditioner heating system doesn't start?
    • Z
      znicholsAug 21, 2025
      If the heating system of your Emerson Air Conditioner does not start and the contactor does not close, check the state of the micro-processing controller to confirm if a heating command is required. Also, use a multimeter to measure the resistance on both ends of the temperature controller. If the resistance is very large, it indicates that the safety device may be open. Then check if the fuse is open and if the temperature controller is damaged. Measure the resistance of the heater with an ohmmeter to judge if the heater is damaged.
  • M
    Michael DiazAug 23, 2025
    How to fix Emerson Air Conditioner compressor over-temperature?
    • W
      whitneymurphyAug 23, 2025
      If your Emerson Air Conditioner compressor is over-temperature, it could be due to a too high compression ratio. Check the settings of the HP switch and LP switch, and make sure whether the condenser is clogged. Check that the fans of the evaporator and condenser are normal. Also, it might be caused by a too high suction overheat degree, so regulate the electronic expansion valve or add the proper amount of refrigerant.
  • Q
    qjenkinsAug 26, 2025
    What to do for high pressure protection on Emerson CR035?
    • K
      Kendra GarciaAug 26, 2025
      If your Emerson Air Conditioner is experiencing high pressure protection issues, the condenser may be clogged, so clean it. Also, check the condensing fan for air-cooled systems to ensure the condenser system starts. Too much refrigerant may have been charged, so verify whether the subcooling degree is too high.
  • D
    Daniel SmithAug 28, 2025
    Why my Emerson CR035 Air Conditioner compressor won’t start?
    • X
      xfisherAug 28, 2025
      The compressor on your Emerson Air Conditioner may not start due to several reasons. First, check the main power for undervoltage, overvoltage, and phase loss. Second, inspect the compressor MCB, contactor, and connecting cables for faults. Third, view the unit alarm records, replace any damaged components, and power it on again. Finally, the compressor coils might be shorted and burnt, so inspect the motor and replace it if you find any defects.
  • R
    Richard KingAug 30, 2025
    What to do if Emerson CR035 has low suction pressure?
    • K
      kyleleAug 30, 2025
      If your Emerson Air Conditioner has low suction pressure or liquid returned, several issues could be the cause. Begin by checking for refrigerant leaks, sealing any leaking points, and adding refrigerant. Next, replace the air filter if it's dirty, or replace the filter drier if it's clogged. Also, check the control board of the electronic expansion valve for improper superheating degree and replace the sensing element if it's faulty. Ensure proper airflow distribution by checking the air supply and return system and verify the condenser isn't faulty due to low condensing pressure.
  • M
    Matthew GraySep 2, 2025
    What to do if contactor does not close and compressor does not start in Emerson CR035?
    • T
      thomasphillipSep 2, 2025
      If the contactor doesn't close and the compressor doesn't start in your Emerson Air Conditioner, check the state of the micro-processing controller for a low discharging overheat degree alarm. Also, check for a high pressure (HP) alarm and refer to Chapter 5. Verify if a discharging low/high temperature alarm exists, and check the history alarm for a low pressure alarm. Ensure the contactor is able to energize and check the compressor driver. Finally, see if the compressor coil is open circuit; if it is, wait until the coil cools down to restore it automatically.
  • J
    Jennifer SmithSep 4, 2025
    Why does my Emerson Air Conditioner compressor stop after 3 minutes?
    • C
      Caroline WeeksSep 5, 2025
      If your Emerson Air Conditioner's compressor stops after running for 3 minutes and the contactor opens, it could be due to refrigerant leakage causing a low or abnormal low pressure check. Verify the suction pressure, check the circuit of the low pressure sensor, and calibrate the low pressure sensor reader to ensure it's within ±0.3bar range of the actual pressure.
  • S
    Scott MartinezSep 7, 2025
    Why is heating ineffective when contactor closes in Emerson CR035?
    • M
      Michaela SchmidtSep 7, 2025
      If the contactor closes but heating is ineffective in your Emerson Air Conditioner, the heater's main power may be off. Check if the heater's MCB is turned ON and verify that L1, L2, and L3 voltages are normal when the contactor is energized. Also, the electric heater might be burned, so turn off the power and physically check its condition.
  • M
    Morgan JacobsSep 9, 2025
    Why is my Emerson Air Conditioner compressor so noisy?
    • J
      Justin GoodSep 10, 2025
      If your Emerson Air Conditioner compressor is too noisy, it could be due to liquid returned. Refer to the handling methods of ‘Low suction pressure or liquid returned.’ It may also be because the bearing is worn out due to lubricant loss, so add lubricant.

Summary

Chapter 1 Overview

Product Introduction

Overview of the CRV+ AC unit's purpose, application, features, and system configuration.

Refrigerant Requirement

Specifies the type and quality of refrigerant required for system operation and warranty.

Chapter 2 Instruction For Pre-installation

Movement, Unpacking, and Inspection

Procedures for safely moving, unpacking, and inspecting the unit upon delivery.

Chapter 5 System Power-On Commissioning

Commissioning Procedures and Checklist

Step-by-step guide for system startup, refrigerant charging, and final inspection.

Chapter 6 Micro-Processing Controller

Advanced Controller Functions and Settings

Details alarm menus, system alarms, sensor settings, temperature/humidity control, and system states.

Chapter 7 System Operation And Maintenance

Routine Maintenance (Monthly and Half-Yearly)

Scheduled inspection and maintenance tasks for various unit components.

Chapter 8 Troubleshooting

Fan Troubleshooting

Common fan issues, possible causes, and troubleshooting steps.

Compressor and Cooling System Troubleshooting

Diagnoses issues related to compressor startup, operation, pressure, and noise.

Emerson CR035 Specifications

General IconGeneral
BrandEmerson
ModelCR035
CategoryAir Conditioner
LanguageEnglish