Application Engineering
B U L L E T I N
AE8-1386 R1
Setup Screens continued
In the C9: Dgtl Scroll tab, the PI algorithm Press Ctrl + 0 to view additional tabs.
for compressor control can be modified. tDs
corresponds to the Digital Compressor Duty
Cycle.
Additional Tabs
d0n = delay between starts of two different loads
LSE = Low limit of compressor setpoint (SETC)
HSE = High limit of compressor setpoint (SETC)
Pb = Proportional band zone width for fan regulation
LSF = Low limit of fan setpoint (SETF)
HSF = High limit of fan setpoint (SETF)
© 2013 Emerson Climate Technologies, Inc.
20
Printed in the U.S.A.