EasyManuals Logo

Emerson CORESENSE User Manual

Emerson CORESENSE
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
© 2018 Emerson Climate Technologies, Inc.
AEX-XXXX
PRELIMINARY
AE8-1384 R6
Table 4 - CoreSense Modbus Map Continued
Parameters can be read using Function code 3 (Read Holding Register)
Location in Hex
Parameter
Message Length in
Bytes
Message Length With
Zero Stuffing
100
Customer Id Code
4
8
104
Customer Location
17
34
115
Customer Name
17
34
126
Compressor Model Number Modified
18
36
138
Compressor serial number
12
24
144
Application code
3
6
147
Temperature code
4
8
14B
Refrigerant code
7
14
152
Functional Configuration
2
2
154
Compressor run time to count as short cycle
1
2
155
Scroll High Temp Trip
2
2
157
Scroll High Temp Reset
2
2
15A
Future Use
1
2
15B
Future Use
2
2
15D
Future Use
2
2
15F
No. of Events to Scroll High Temp Lockout
1
2
160
No. of Events to Short Cycling Warning/Lockout
1
2

Other manuals for Emerson CORESENSE