Emerson Dixell Wing XW570K - FANS; ALARMS; ANALOGUE OUTPUT 4+20 mA (Optional); ANALOGUE INPUTS

Emerson Dixell Wing XW570K
6 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592009630 XW570K GB r1.0 04.08.2015 XW570K 6/6
Label
Name
Range
Default
Level
FANS
FnC
Fans operating mode
C-n, C-y, O-n, O-y
O-n
Pr2
Fnd
Fans delay after defrost
0÷255 min.
10
Pr2
FSt
Fans stop temperature
-50,0÷110°C / -58÷230°F
2/35
Pr2
ALARMS
ALC
Temperature alarms configuration
rE÷Ab
rE
Pr2
ALU
MAXIMUM temperature alarm
-50,0÷110°C/-58÷230°F
10/20
Pr1
ALL
minimum temperature alarm
-50,0÷110°C/ -58÷230°F
10/20
Pr1
AFH
Temperature alarm and fan differential
0,1÷25,5 °C/ 1÷45°F
2/4
ALd
Temperature alarm delay
0÷255 min.
15
Pr2
dAO
Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1,3
Pr2
EdA
Alarm delay at the end of defrost
0÷255 min.
30
Pr2
dot
Delay of temperature alarm after closing the door
0÷255 min.
15
Pr2
dOA
Open door alarm delay
0÷254 min., nu
15
Pr2
tBA
Alarm relay silencing
y ÷ n
y
Pr2
nPS
Pressure switch activation number
0÷15
0
Pr2
ANALOGUE OUTPUT
4÷20mA (Optional)
AOS
Analogue output start point
-50,0÷110°C / -58÷230°F
0/32
Pr2
APb
Analogue output band width
-50,0÷110°C / -58÷230°F
0
Pr2
CAO
Input type for the analogue output
P1÷1r2
P1
Pr2
ANALOGUE INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr1
OE
Evaporator probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
O3
Auxiliary probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
P2P
Evaporator probe presence
n ÷ y
y
Pr2
P3P
Auxiliary probe presence
n ÷ y
n
Pr2
HES
Temperature increase during the Energy Saving
cycle
-30÷30°C / -54÷54°F
0
Pr2
DIGITAL INPUTS
Odc
Open door control
no, Fan, CPr, F_C
Fan
Pr2
I1P
Door switch polarity
CL÷OP
CL
Pr2
I2P
Configurable digital input polarity
CL÷OP
CL
Pr2
i2F
Digital input configuration
EAL, bAL, PAL,
dFr, AUS, ES, OnF
EAL
Pr2
dId
Digital input alarm delay
0÷255 min.
5
Pr2
TIME AND WEEKLY HOLIDAYS
°C/°F
XW570
Hur
Current hour
0 ÷ 23
0
Pr2
Min
Current minute
0 ÷ 59
0
Pr2
dAY
Current day
Sun ÷ SAt
Sun
Pr2
Hd1
First weekly holiday
Sun ÷ SAt nu
nu
Pr2
Hd2
Second weekly holiday
Sun ÷ SAt nu
nu
Pr2
Hd3
Third weekly holiday
Sun ÷ SAt nu
nu
Pr2
ENERGY SAVING TIMES
ILE
Energy Saving cycle start during workdays
0 ÷ 23h 50 min.
0
Pr2
dLE
Energy Saving cycle length during workdays
0 ÷ 24h 00 min.
0
Pr2
ISE
Energy Saving cycle start on holidays
0 ÷ 23h 50 min.
0
Pr2
dSE
Energy Saving cycle length on holidays
0 ÷ 24h 00 min.
0
Pr2
HES
Temperature increase during the Energy Saving
cycle
-30÷30°C / -54÷54°F
0
Pr2
DEFROST TIMES
Ld1
1
st
workdays defrost start
0 ÷ 23h 50 min. - nu
6.0
Pr2
Ld2
2
nd
workdays defrost start
0 ÷ 23h 50 min. - nu
13.0
Pr2
Ld3
3
rd
workdays defrost start
0 ÷ 23h 50 min. - nu
21.0
Pr2
Ld4
4
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld5
5
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld6
6
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld7
7
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld8
8
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd1
1
st
holiday defrost start
0 ÷ 23h 50 min. - nu
6.0
Pr2
Sd2
2
nd
holiday defrost start
0 ÷ 23h 50 min. - nu
13.0
Pr2
Sd3
3
rd
holiday defrost start
0 ÷ 23h 50 min. - nu
21.0
Pr2
Sd4
4
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd5
5
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd6
6
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd7
7
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd8
8
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
OTHER
Adr
Serial address
0÷247
1
Pr1
rEL
Software release
- - -
- - -
Pr2
Label
Name
Range
Default
Level
Ptb
Map code
- - -
- - -
Pr2
Prd
Probes display
Pb1÷Pb3
- - -
Pr2
Pr2
Access parameter list
- - -
- - -
Pr2