13.1 SILENCING BUZZER / ALARM RELAY OUTPUT
If “tbA = y”, once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key.
If “tbA = n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers.
Buzzer is mounted in the T850 keyboards and it is an option.
13.2 “EE” ALARM
The Dixell instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a
failure in the memory data occurs. In such cases the alarm output is enabled.
13.3 ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal
operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal
values or when the defrost starts.
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled “PAL” alarm is recovered by
switching OFF the instrument.
14. TECHNICAL DATA
T850 keyboards
Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 23mm
Mounting :
panel mounting in a 150x31 mm panel cut-out with two screws.
3 x 2mm.
Distance between the holes 165mm
Protection: IP20.
Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block
2,5 mm
2
heat-resistant wiring and 6,3mm
Power supply: from power module
Display: 3 digits, red LED, 14,2 mm high.
Optional output: buzzer
Power modules XW570K
Case:
“OS”: open board 132x 94 mm; height: 40mm.
“OA”: open board with aluminium protection 176x 123mm; height: 52mm.
“GS”: case 155x114; height 70mm. Self extinguishing ABS. IP55
“PS”: case 147x110; height 47mm. Self extinguishing ABS. IP55. UL approved
Connections: Screw terminal block
2,5 mm
2
heat-resistant wiring and 6,3mm Faston
Power supply: 230Vac or. 110Vac
10%
Power absorption: 10VA max.
Inputs: 3 NTC probes
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 16(3) A, 250Vac (or optional relay SPST 16(3) A, special for fluorescent lights)
fans: relay SPST 8(3) A, 250Vac
defrost: relay SPST 8(3) A, 250Vac
alarm: SPST relay 8(3) A, 250Vac
auxiliary: SPST relay 16(3) A, 250Vac
Other output :
Analogue output 4÷20 mA (optional)
Serial output : TTL standard. RS485 optional
Communication protocol: ModBUS - RTU
Data storing: on the non-volatile memory (EEPROM).
Internal clock back-up: 24 hours
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20
85% (no condensing)
Measuring and regulation range:
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
15. CONNECTIONS
15.1 XW570K
+ :connection for keyboard
- : connection for keyboard
Configurable digital input
16. DEFAULT SETTING VALUES
SET ÷ 110°C / SET ÷ 230°F
Outputs activation delay at start up
Compressor ON time during fast freezing
Compressor ON time with faulty probe
Compressor OFF time with faulty probe
Temperature measurement unit
Resolution (integer/decimal point)
Set point for SMART DEFROST
Defrost termination temperature (1°Evaporator)
Interval between defrost cycles
(Maximum) length for 1° defrost
Displaying during defrost
MAX display delay after defrost
First defrost after start up
Defrost delay after fast freezing