How to fix over-current during acceleration in Emerson EV2000-4T0300G1/0370P1?
- KKelly HayesAug 21, 2025
If you're experiencing over-current during acceleration with your Emerson DC Drives, it could be due to several reasons. The acceleration time might be too short, so try prolonging it. The V/F curve may not be suitable; in this case, check and adjust the V/F curve and torque boost, or correctly set the motor parameters to ensure normal auto torque boost. If the motor restarts right after stopping, set F2.00 to the “start on fly” function. Also, check the drive’s input AC supply in case of low voltage, or consider that the drive power may be insufficient, and you might need to select a higher power drive.