34      Chapter 3  Installation and Wiring 
EV2000 Series Universal Variable Speed Drive    User Manual 
high frequency terminal. The paints on the bolt should 
be cleaned. 
The earthing cable should be as short as possible, that 
is, the earthing point should be as close to the drive as 
possible. 
Earthing cables should be as far away from the I/O 
cables of the equipment that is sensitive to noise, and 
also should be as short as possible. 
3.4.4    Installation Requirements of Relay, Contactor and 
Electro-magnetic Braking Kit 
The devices such as relay, contactor and 
electro-magnetic braking kit, which may generate great 
noises, should be installed outside of the drive cabinet 
and should be installed with surge suppressors. 
220VAC
Varistor
Diode
Inverter
220VAC
RC-Filter
+24VDC
 
Fig. 3-41    Relay, contactor and electro-magnetic braking kit 
3.4.5  Leakage Current 
Leakage current may flow through the drive’s input and 
output capacitors and the motor’s capacitor. The 
leakage current value is dependent on the distributed 
capacitance and carrier wave frequency. The leakage 
current includes ground leakage current and the leakage 
current between lines. 
AC supply
Drive
Distributed 
capacitor 
between lines
Motor
Distributed 
capacitor between 
cable and earth
Capacitor 
between 
motor and 
earth
R
S
T
QF
 
Fig. 3-42 Flowing path of leakage current 
Ground leakage current 
The ground leakage current can not only flow into the 
drive system, but also other equipment via earthing 
cables. It may cause the leakage current circuit breaker 
and relays falsely activated. The higher the drive’s 
carrier wave frequency, the bigger the leakage current, 
also, the longer the motor cable, the greater the leakage 
current, 
Suppressing methods: 
Reduce the carrier wave frequency, but the motor noise 
may be louder; 
Motor cables should be as short as possible; 
The drive and other equipment should use leakage 
current circuit breaker designed for protecting the 
product against high-order harmonics/surge leakage 
current; 
Leakage current between lines 
The line leakage current flowing through the distribution 
capacitors of the drive out side may cause the thermal 
relay falsely activated, especially for the drive whose 
power is lower than 7.5kW. When the cable is longer 
than 50m, the ratio of leakage current to motor rated 
current may be increased that can cause the wrong 
action of external thermal relay very easily. 
Suppressing methods: 
Reduce the carrier wave frequency, but the motor noise 
may become louder; 
Install reactor at the output side of the drive. 
In order to protect the motor reliably, it is recommended 
to use a temperature sensor to detect the motor’s 
temperature, and use the drive’s over-load protection 
device(electronic thermal relay) instead of an external 
thermal relay. 
3.4.6  Correct EMC Installation 
Divide the installation space into different areas 
In driving system, the drive, control equipment and 
sensors are installed in the same cabinet, the noise 
should be suppressed at the main connecting points 
with the RFI filter and input reactor installed in cabinet to 
satisfy the EMC requirements. 
The most effective but expensive measure to reduce the 
interference is to isolate the noise source and the noise 
receiver, which should be considered in 
mechanical/system design phase. In driving system, the 
noise source can be drive, brake unit and contactor. 
Noise receiver can be automation equipment, coder and 
sensor. 
The mechanical/system is divided into different EMC 
area according to its electrical characteristics. The 
recommended installation positions are shown in the 
following figure: