AGL_Sol_EV3_E_Rev_02    19 
Based  on  the  compressor  envelope  and  the  speed  range  selection  (see  paragraph  5.2.7 
"Compressor speed range selection") it can happen that low speed demands will be ignored. 
5.2.6  Shutdown conditions 
The drive will stop in heating as well as in running mode if one of below conditions occurs: 
▪  system or drive fault is detected; 
▪  enable signal is gone; 
▪  analog signal gets lower than 0.5 V. 
5.2.7  Compressor speed range selection 
With a bridge on terminal L (CN104) the full application envelope speed range is usable in normal 
operation. In this case the main controller must have a proper envelope control implemented. Without 
this bridge, the drive will limit the lowest speed to MMS. 
 
Figure 11: Analog board speed range selection 
In speed-drop-protection mode the drive will only use the limited speed range. In this case the speed 
will not go below the MMS speed. 
5.2.8  Onboard 7-segment display 
The onboard 7-segment display shows the main information about the drive compressor status, 
failure and warning codes which are part of Table 19. 
Alternating between selected drive 
compressor code (ie, C023) and 
software version (ie, S04.8) 
Shows the selected power in % 
between 0 and 100 % (H-00, H100) 
Alternating between the compressor 
speed and the root cause (ie, Sd06) 
shown in Table 19.