22 AGL_Sol_EV3_E_Rev_02
6.4 Speed drop protection limits, LED and analog board codes
In case of failure, the alarm code is visible at the signal LED. The number of blinks is equal to the
alarm code.
No
Alert and fault
message
Static, dynamic and recovery
limits
Protective
action
Analog
board
Alarm
code
#OneEmerson
Register bit
1
Drive power under
voltage
N/A
Compressor
trip
-
5
-
2
DC overvoltage
Limit / recovery
800 V / 720 V
Compressor
trip
E03
6
80.2
3
DC undervoltage
Limit / recovery
300 V / 380 V
Compressor
trip
E04
7
80.3
4
AC input undervoltage
Limit / recovery
295 V / 325 V
Compressor
trip
E06
11
80.5
5
Drive module
overtemperature
Limit / recovery
EV3150B: 110 °C / 85 °C
EV3185B: 110 °C / 85 °C
Compressor
trip
E12
12
80.11
6
Compressor DLT
overtemperature
Limit / recovery
135 °C / 115 °C
Compressor
trip
E25
13
81.8
7
Communication fault
30 seconds
Compressor
trip
E24
14
81.7
8
EEPROM fault
EEPROM CRC incorrect
Compressor
trip
E37
15
84.4
9
Wrong compressor code
N/A
Compressor
trip
E39
16
84.6
10
Output U phase current
sampling fault
N/A
Compressor
trip
E44
17
84.11
11
Output V phase current
sampling fault
N/A
Compressor
trip
E10
18
80.10
12
Output W phase current
sampling fault
N/A
Compressor
trip
E10
19
80.10
13
Input current sampling
fault
Input current AD < 1658 or
input current AD > 2487
Compressor
trip
-
20
-
14
Drive module
temperature sampling
fault
If the module temperature read from
the ADC is:
ADC_temp < 38 or ADC_temp > 2900
Compressor
trip
E54
21
85.5
15
DLT temperature
sampling fault
If the DLT temperature read from the
ADC is:
ADC_temp < 64 or ADC_temp > 2650
Compressor
trip
E51
22
85.2
16
Compressor loss of
motor control
If compressor estimated speed is
below 0, or compressor voltage is
below 15 V for 1 second
Compressor
trip
E11
23
80.10
17
Compressor overspeed
N/A
Compressor
trip
-
24
-
18
Envelope timeout
-
-
-
27
-
19
Module temperature
foldback timeout
Speed-drop protection limit /
recovery value
EV3150B, EV3185B: 108 °C / 103 °C
Compressor
speed drop
E20
28
81.3
20
Input current foldback
timeout
Speed-drop protection limit /
recovery value
EV3150B: 30 A / 28 A
EV3185B: 41 A / 39 A
Compressor
speed drop
-
29