personal injury and property damage 
due to bursting of pressure-containing 
parts. To avoid such injury and damage, 
install the regulator in a safe location.
1.  Use qualied personnel when installing, operating 
and maintaining pilots. Before installing, inspect 
pilot and tubing, for any shipment damage or 
foreign material that may have collected during 
crating and shipment. Make certain that body is 
clean and the pipelines are free of foreign material.
!
WARNING
In hazardous or ammable gas service, 
vented gas may accumulate and cause 
personal injury, death or property 
damage due to re or explosion. Vent 
a regulator in hazardous gas service 
to a remote, safe location away from 
air intakes or any hazardous location. 
The vent line or stack opening must 
be protected against condensation 
or clogging.
2.  Pilots have a 1/4 NPT vent connection in the 
spring case. To remotely vent gas from the spring 
case, remove the screened vent and connect 
1/4 in. / 6.4 mm piping or tubing. It should vent to 
a safe location, have as few elbows as possible 
and have a screened vent on its exhaust. Install 
the regulator and any remote vent spring or tubing 
so that the vent is protected from condensation, 
freezing or substance that may clog it.
CAUTION
To avoid freeze-up because of pressure 
drop and moisture in the gas, use 
anti-freeze practices, such as heating 
the supply gas or adding a de-icing 
agent to the supply gas.
3.  Run a 3/8 in. / 9.5 mm outer diameter or larger 
pilot supply line from the upstream pipeline to the 
lter inlet, bushing the line down to t the 1/4 NPT 
lter connection. Do not make the upstream 
pipeline connection in a turbulent area, such as 
near a nipple, swage or elbow. If the maximum 
pilot inlet pressure could exceed the pilot rating, 
install a separate pressure reducing regulator in 
the pilot supply line. Install a hand valve in the pilot 
supply line and provide vent valves to properly 
isolate and relieve the pressure from the regulator.
4.  Attach a 1/2 in. / 13 mm piping or tubing 
downstream control line to the 1/2 NPT control 
line connection on the actuator casings. Connect 
the other end of the control line to the pipeline 
downstream of the regulator. Do not attach the 
control line near any elbow, swage, block valve 
or any other location that might cause turbulence. 
Install a full port ball valve in the control line 
to shut off the control pressure when using 
the bypass.
Startup and Adjustment
Pre-Startup Considerations
Each regulator is factory-set for the outlet pressure 
specied on the order. If no setting was specied, 
outlet pressure was factory-set at the mid-range of 
the pilot control spring. Before beginning the startup 
procedure in this section, make sure the following 
conditions are in effect:
•  Block valves isolate the regulator
•  Vent valves are closed
•  A bypass, if any, is in operation
In all cases, check the control spring setting to make 
sure it is correct for the application.
CAUTION
Be sure to slowly introduce pressure 
into the system to prevent downstream 
overpressure due to potential rapid 
pressure increase. Pressure gauges 
should always be used to monitor 
downstream pressure during startup. 
Procedures used in putting this 
regulator into operation must be planned 
accordingly if the downstream system is 
pressurized by another regulator or by a 
manual bypass.
Pilot Adjustment
For 161 Series pilots, remove the pilot closing cap 
(key 16, Figures 4 through 6 or key 22, Figure 7) 
and, on 161EB Series only, loosen the locknut 
(key 12, Figure 4). Turn the adjusting screw (key 11, 
Figures 4 through 6 or key 35, Figure 7) into the 
4
161 Series