Instruction Manual
D200156X012
4194HA, HB, HC Controllers
July 2018
7
Table 1‐3. Process Sensor (Barton 199) Range and Pressure Ratings
DIFFERENTIAL PRESSURE RANGE
(1)
SAFE WORKING PRESSURE
(2)
HOUSING
MATERIAL
Bar Psig
Psig (bar)
0 to 15 (0 to 1)
0 to 30 (0 to 2)
0 to 40 (0 to 2.8)
0 to 50 (0 to 3.4)
0 to 60 (0 to 4)
0 to 75 (0 to 5)
68.9 1000 Stainless steel
0 to 15 (0 to 1)
0 to 30 (0 to 2)
0 to 40 (0 to 2.8)
0 to 50 (0 to 3.4)
0 to 60 (0 to 4)
0 to 75 (0 to 5)
172 2500 Steel
0 to 15 (0 to 1)
0 to 30 (0 to 2)
0 to 40 (0 to 2.8)
0 to 50 (0 to 3.4)
0 to 60 (0 to 4)
0 to 75 (0 to 5)
414 6000 Steel
Inches w.c. (mbar)
0 to 20 (0 to 50)
0 to 25 (0 to 62)
0 to 50 (0 to 124)
0 to 75 (0 to 186)
0 to 100 (0 to 248)
68.9 1000 Stainless steel
0 to 20 (0 to 50)
0 to 25 (0 to 62)
0 to 50 (0 to 124)
0 to 75 (0 to 186)
0 to 100 (0 to 248)
172 2500 Steel
0 to 20 (0 to 50)
0 to 25 (0 to 62)
0 to 50 (0 to 124)
0 to 75 (0 to 186)
0 to 100 (0 to 248)
414 6000 Steel
1. Differential pressure ranges are in English units of measurement; metric equivalents are shown here for reference only. Consult your Emerson sales office or Local Business Partner for special
differential pressure ranges.
2. The Barton 199 differential pressure unit may be pressured to this value without permanent zero shift or structural damage to controller components.
Table 1‐4. Supply Pressure Requirements
Output Signal Range Normal Operating Supply Pressure
(1)
Maximum Pressure to Prevent
Internal Damage
(2)
Bar
0.2 to 1.0 1.4 2.8
0.4 to 2.0 2.4 2.8
Psig
3 to 15 20 40
6 to 30 35 40
1. If this pressure is exceeded, control stability may be impaired.
2. If this pressure is exceeded, damage to the controller may result.