EasyManuals Logo
Home>Emerson>Controller>Fisher Fieldvue DVC6010f

Emerson Fisher Fieldvue DVC6010f User Manual

Emerson Fisher Fieldvue DVC6010f
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #215 background imageLoading...
Page #215 background image
DO Function Block
March 2006
5-149
considered a logic 1. With this option disabled, OUT_D
[9] is a direct copy of SP_D [8]. The readback value is
processed through the Invert option to become PV_D
[7]. The Use PV for BKCAL_OUT option specifies that
BKCAL _OUT equal the value of the process variable
(PV_D [7]) instead of the set point (SP_D [8]). If you
do not enable this option, BKCAL_OUT will equal
SP_D [8].
Output Block PV Status
The Output Block PV Status is determined by the
enabled status of the Resource Block parameter
FEATURE_SEL [18], the Transducer Block mode, and
enabled Active PlantWeb alarms. Refer to table 5-1.
Block Errors
Table 5-70 lists conditions reported in the
BLOCK_ERR [6] parameter. Conditions in italics are
not applicable for the DO block and are provided only
for your reference.
Action on Fault Detection
Fault State is caused by one of three sources: A
status pertaining to CAS, A status pertaining to RCAS,
or SET_FSTATE [29] in the resource block. To
implement Fault State, configure the following
parameters:
IO_OPTS [14]: Determines the action OUT_D [9] will
take upon a fault state. If the IO_OPTS [14] “Fault
State to Value” is not selected, then OUT_D [9] holds
its last position when Fault State is set. If “Fault State
to Value” is selected, OUT_D [9] goes to the
FSTATE_VAL_D [20] value when Fault State is set.
FSTATE_TIME [19]: The length of time, in seconds,
that the DO block will wait to set Fault State. When
Table 5-70. BLOCK_ERR Conditions
Condition
Number
Condition Name and Description
0 Other (N/A)
1
Block Configuration Error - SHED_OPT or CHANNEL set to
0 (uninitialized)
2 Link Configuration Error (N/A)
3
Simulate active - Simulation is enabled and the block is using
a simulated value in its execution.
4 Local Override - Device in fault state. Actual mode LO.
5
Device Fault State Set - DO block in fault state after
FSTATE_TIME because of Bad status or IFS substatus on
CAS_IN_D or Resource block commanded fault state.
6
Device Needs Maintenance Soon - Indicates a Maintenance
PlantWeb Alert condition is active if Block Error Reporting is
enabled. See page 5-39.
7
Input failure/process variable has Bad status - PV has bad
status and Feature Select in the Resource block has the Out
Readback bit set or the transducer block mode is Out of
Service.
8
Output failure - PV has bad status or the transducer block
mode is Out of Service.
9 Memory Failure (N/A)
10 Lost Static Data (N/A)
11 Lost NV Data (N/A)
12 Readback Check Failed (N/A)
13
Device Needs Maintenance Now - Indicates Failed
PlantWeb Alert condition is active if Block Error Reporting is
enabled. See page 5-39.
14
Power Up - This condition exists after power up until actual
mode is not Out of Service.
15 Out of Service - The block is in Out of Service (OOS) mode.
Fault State is set, the OUT_D [9] value goes to either
the FSTATE_VAL_D [20] value or holds its last
position, depending on I/O_OPTS [14]. When the
block has a target mode of CAS, a fault condition will
be detected if the CAS_IN_D [17] has a BAD status or
an Initiate Fault State substatus is received from the
upstream block.
FSTATE_VAL_D [20]: Determines the OUT_D [9]
value if IO_OPTS [14] “Fault State to Value” is
selected. The OUT_D [9] value transitions to
FSTATE_VAL_D [20] after FSTATE_TIME [19]
elapses and the fault condition has not cleared.
Simulation
To support testing of the control strategy, you can
enable the SIMULATE_D [17] parameter. Normally,
the valve position value and status used for
READBACK_D [16] in the DO block reflect actual
process values to the nearest 5%, as provided by the
transducer block. When the SIMULATE_D [17]
parameter is enabled, value and status used for
READBACK_D [16] is supplied by the user manually.
To enable simulation in the DO function block, the
simulate jumper must be installed. For information on
the installation of this jumper, see the page 2-25
Installation section.
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6010f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6010f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6010f
CategoryController
LanguageEnglish

Related product manuals