Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
32
Smart Wireless THUM Adapter
Refer to the Smart Wireless THUM Adapter quick installation guide (0082501004075) for additional information.
Note
The recommended mounting orientation for the THUM Adapter is vertically up, as shown in figure 26, for optimal wireless
communication range.
Figure 26. THUM Adapter Installed On DVC6200 Digital Valve Controller
TOP CONDUIT
ENTRANCE
X0433
1. Remove the DVC6200 terminal box plug from the top conduit entrance.
2. Thread the THUM Adapter into the top conduit entrance.
3. Using the wire splice included with the THUM Adapter (or other suitable wire splice), connect the wires as shown in
figure 27 below.
Figure 27. Wiring the THUM Adapter
GG18677
THUM ADAPTER
GREEN
RED
BLACK
WHITE
YELLOW
WIRED DEVICE
LOOP -
LOOP +
SPLICE
CONNECTOR
GROUND
4-20 mA
4-20 mA
LOOP -
LOOP +
4. Carefully coil the wires inside the terminal box.
5. Replace and hand tighten the cover on the terminal box.
6. Proceed to Step 4—Configure the Digital Valve Controller on page 33.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 HW1 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 HW1 Specifications

General IconGeneral
ManufacturerEmerson
ModelFIELDVUE DVC6200 HW1
TypeDigital Valve Controller
Input Signal4-20 mA DC
Communication ProtocolHART
Operating Temperature Range-40 to 85°C (-40 to 185°F)
Enclosure RatingNEMA 4X, IP66
MaterialAluminum or Stainless Steel
CertificationsATEX, IECEx, FM, CSA
DiagnosticsAdvanced diagnostics capabilities

Related product manuals