Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
47
Figure 39. CSA Loop Schematics FIELDVUE DVC6205, DVC6205 SIS, and DVC6215
1 SEE NOTES IN FIGURE 42
GE42818 Sheet 12, Rev. C
CLASS I, ZONE 0, GROUP IIC
CLASS I, DIV 1, GROUPS ABCD
CLASS II, DIV 1, GROUPS EFG
CLASS III
REMOTE
FIELD WIRING
TERMINAL BOX
HAZARDOUS LOCATION
POWER MAY BE APPLIED TO EITHER
THE LOOP TERMINALS OR OUTPUT
TERMINALS OR TO BOTH SETS OF
TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE
WILL NOT HAVE “OUTPUT TERMINALS”
AVAILABLE FOR CONNECTION
NOTE 7
T CODE T (amb) T (amb)
T5 80_C 80_C
1
NON‐HAZARDOUS LOCATION
CSA APPROVED BARRIER
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6205
NOTE 1, 3, 4, 5, 6 1
T6 61_C 74_C
CSA APPROVED BARRIER
NOTE 1, 3, 4, 5, 6 1
DVC6215
Vmax = 30 VDC
Imax = 226 mA
Ci = 50 nF
Li = 0.55 mH
Pi = 1.4 W
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
CLASS I, ZONE 0, GROUP IIC
CLASS I, DIV 1, GROUPS ABCD
CLASS II, DIV 1, GROUPS EFG
CLASS III
Voc = 30 VDC
Isc = 21.2 mA
Ca = 55 nF
La = 78 mH
Po = 160 mW
LOOP TERMINALS
Vmax = 30 VDC
Imax = 130 mA
Ci = 15 nF
Li = 0.55 mH
Pi = 1.0 W
OUTPUT TERMINALS
Vmax = 28 VDC
Imax = 100 mA
Ci = 15 nF
Li = 0.5 mH
Pi = 1.0 W
FIELD WIRING
TERMINAL BOX
T CODE T (amb)
T5 90_C
T6 75_C
T4 125_C
NOTE 1, 3 1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 HW1 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 HW1 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6200 HW1
CategoryController
LanguageEnglish

Related product manuals