Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
58
ATEX
Flameproof II 2 G
WARNING
Do not open while energized.
Potential electrostatic charging hazard. See warning on page 3.
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION FIELDBUS, PROFIBUS)
Ex d IIC T5 (Ta ≤ 85°C)
Ex d IIC T6 (Ta ≤ 80°C)
Operating ambient temperature
 Standard construction -40_C to +85_C,
 Extreme temperature construction -52_C to +85_C
Type n II 3 G
WARNING
Do not open while energized.
Potential electrostatic charging hazard. See warning on page 3.
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION FIELDBUS, PROFIBUS)
Ex nC IIC T5 (Ta ≤ 80°C)
Ex nC IIC T6 (Ta ≤ 75°C)
Operating ambient temperature
Standard construction -40_C to +80_C,
Extreme temperature construction -52_C to +80_C
Intrinsically Safe
WARNING
Potential electrostatic charging hazard. See warning on page 3.
DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION FIELDBUS, PROFIBUS)
II 1 GD
Operating ambient temperature
Standard construction -40_C to +80_C,
Extreme temperature construction -52_C to +80_C
DVC6215
II 1 G
- 52_C Ta + 125_C