EasyManua.ls Logo

Emerson Fisher LR125 - Type LR125 Troubleshooting Guide

Emerson Fisher LR125
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Type LR125
14
Table 8. Troubleshooting Guide
ISSUE POSSIBLE SOLUTION
Outlet pressure suddenly rises above
setpoint and approaches inlet pressure
If travel indicator is in UP position, check restrictor and pilot supply lter for plugging.
If travel indicator is in DOWN position, check main valve for debris or diaphragm damage.
Outlet pressure normal at low ow but
falls below setpoint at high ow
Check main valve inlet strainer for plugging.
Check inlet pressure at high ow condition.
Check sizing calculations to be sure main valve body is large enough for load.
Check for undersized or restricted control line (use the minimum size given in step 6 of Type LR125
Installation section).
Adjust restrictor to a lower setting.
Outlet pressure cycles
Adjust restrictor to a higher setting.
Check control line placement. Make sure it is not located in a turbulent area.
Make sure there is not a restriction in the control line, such as a needle valve.
Fluid leaks from pilot spring case Replace pilot diaphragm assembly.
Fluid leaks from travel indicator Replace indicator stem O-ring, if indicator is not desired, convert to a non-travel indicator assembly.
Outlet pressure approaches inlet
pressure when no ow is desired
Check main valve O-rings for damage or improper installation.
Check cage and diaphragm surfaces for erosion or trapped debris.
Check pilot valve plug and seat for seating surface damage or debris.
Check pilot for trapped debris.
Regulator will not open
Check for clogged control line.
Make sure control line is installed and open.
Check for damage to the main valve diaphragm.
On new installations, make sure the control line and pilot supply are properly connected.
Regulator will not close
Make sure the pilot supply is properly connected.
Check restrictor for clogging.
Check the main valve diaphragm for damage.
Check for a broken control line.
High lock-up pressure with slow shutdown Check for debris on main valve or pilot seat.
High lock-up pressure with fast shutdown Adjust restrictor to a higher setting.
Note: If you were unable to solve your problem using this troubleshooting guide, contact your local Sales O󰀩ce.
Table 9. Type LR125 Torque Values
BODY SIZE,
In. / DN
CAP SCREWS (KEY 3) OR
HEX NUTS (KEY 47)
FLANGED HEX NUT (KEY 13) OR
SOCKET HEAD SCREW
(KEY 129, 1 IN. / DN 25 ONLY)
INDICATOR FITTING OR
INDICATOR PLUG (KEY 19)
Ft-lbs / N•m
1 / 25 75 to 95 / 102 to 129 4 to 6 / 5.5 to 8 90 to 160 / 122 to 217
2 / 50 55 to 70 / 75 to 95 10 to 14 / 14 to 19 90 to 160 / 122 to 217
3 / 80 100 to 130 / 136 to 176 32 to 40 / 44 to 54 200 to 300 / 271 to 407
4 / 100 160 to 210 / 217 to 285 32 to 40 / 44 to 54 200 to 300 / 271 to 407
Table 10. Type MR95H/MR95HP Pilot Torque Values
BODY SIZE,
In. / DN
SPRING CASE BOLTS (KEY 16) ORIFICE (KEY 3) VALVE PLUG GUIDE (KEY 5)
Ft-lbs / N•m
1/2 / 15 10 to 13 / 14 to 18 34 to 38 / 46 to 51 75 to 90 / 102 to 122

Related product manuals