Instruction Manual
D103576X012
January 2020
Type LR125
!
WARNING
Type LR125 Pressure Reducing Liquid Regulator
TYPE LR125 REGULATOR TYPE MR95H/MR95HP PILOT
Figure 1. Type LR125 Pressure Reducing Liquid Regulator and Type MR95H/MR95HP Pilot
Failure to follow these instructions or
to properly install and maintain this
equipment could result in bursting
of the equipment and/or chemical
contamination causing property damage
and personal injury or death.
Fisher™ regulators must be installed,
operated and maintained in accordance
with federal, state and local codes, rules
and regulations and Emerson Process
Management Regulator Technologies,
Inc. (Emerson) instructions.
If the regulator discharges process
uid or a leak develops in the system,
service to the unit may be required.
Failure to correct trouble could result in
a hazardous condition.
Call a qualied service person to service
the unit. Installation, operation and
maintenance procedures performed
by unqualied personnel may result
in improper adjustment and unsafe
operation. Either condition may result in
equipment damage or personal injury.
Only a qualied person must install or
service the regulator.
The Type LR125 is designed for liquid
service. Do not operate the regulator
in applications where temperatures are
below the process uid’s freezing point
or above its boiling point which are
dependent on the process uid and the
application pressures.
Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher LR125 and is the answer not in the manual?

Summary

Type LR125 Specifications

Type LR125 Construction Materials

Details the materials used for the Type LR125 main valve and pilot components.

Type LR125 Pilot Type Description

Describes the MR95H and MR95HP pressure reducing pilots used with the Type LR125.

Type LR125 Operation and Installation

Type LR125 Principle of Operation

Explains how the Type LR125 pressure reducing liquid regulator functions.

Type LR125 Installation Guidelines

Provides critical safety and procedural guidance for installing the Type LR125 regulator.

Startup, Adjustment, and Shutdown

Type LR125 Startup Procedure

Step-by-step instructions for safely starting up the Type LR125 regulator.

Type LR125 Pilot Adjustment

Guidance on adjusting the outlet pressure setting of the pilot for the Type LR125.

Type 112 Restrictor Setting Guide

Recommendations for setting the Type 112 restrictor for optimal regulator performance.

Type LR125 Shutdown Procedure

Instructions for safely shutting down and isolating the Type LR125 regulator.

Maintenance and Troubleshooting

Type LR125 Main Valve Trim Parts

Details on the parts for the Type LR125 main valve trim and their references.

Type LR125 Disassembly and Assembly

Procedures for safely disassembling and reassembling the Type LR125 regulator.

Diaphragm and Plug Assembly Maintenance

Instructions for maintaining or replacing the diaphragm and plug assembly.

Travel Indicator Assembly Maintenance

Procedures for maintaining the travel indicator assembly of the Type LR125.

Pilot Maintenance Procedures

Maintenance instructions for the Type MR95H and MR95HP pilots.

Type LR125 Troubleshooting Guide

A guide to identify and resolve common issues with the Type LR125 regulator.

Type 112 Restrictor Maintenance

Procedures for maintaining the Type 112 restrictor, including cleaning.

Type LR125 Parts Ordering and List

Information on ordering replacement parts and a list of available parts.

Summary

Type LR125 Specifications

Type LR125 Construction Materials

Details the materials used for the Type LR125 main valve and pilot components.

Type LR125 Pilot Type Description

Describes the MR95H and MR95HP pressure reducing pilots used with the Type LR125.

Type LR125 Operation and Installation

Type LR125 Principle of Operation

Explains how the Type LR125 pressure reducing liquid regulator functions.

Type LR125 Installation Guidelines

Provides critical safety and procedural guidance for installing the Type LR125 regulator.

Startup, Adjustment, and Shutdown

Type LR125 Startup Procedure

Step-by-step instructions for safely starting up the Type LR125 regulator.

Type LR125 Pilot Adjustment

Guidance on adjusting the outlet pressure setting of the pilot for the Type LR125.

Type 112 Restrictor Setting Guide

Recommendations for setting the Type 112 restrictor for optimal regulator performance.

Type LR125 Shutdown Procedure

Instructions for safely shutting down and isolating the Type LR125 regulator.

Maintenance and Troubleshooting

Type LR125 Main Valve Trim Parts

Details on the parts for the Type LR125 main valve trim and their references.

Type LR125 Disassembly and Assembly

Procedures for safely disassembling and reassembling the Type LR125 regulator.

Diaphragm and Plug Assembly Maintenance

Instructions for maintaining or replacing the diaphragm and plug assembly.

Travel Indicator Assembly Maintenance

Procedures for maintaining the travel indicator assembly of the Type LR125.

Pilot Maintenance Procedures

Maintenance instructions for the Type MR95H and MR95HP pilots.

Type LR125 Troubleshooting Guide

A guide to identify and resolve common issues with the Type LR125 regulator.

Type 112 Restrictor Maintenance

Procedures for maintaining the Type 112 restrictor, including cleaning.

Type LR125 Parts Ordering and List

Information on ordering replacement parts and a list of available parts.

Overview

The Type LR125 is a pilot-operated, pressure-reducing liquid regulator designed for liquid applications. It includes a Type 112 restrictor and a 1/2 NPT Type MR95H/MR95HP pilot. The regulator's primary function is to maintain a desired outlet (control) pressure by adjusting the main valve's opening in response to changes in downstream pressure.

Function Description

The Type LR125 operates on a principle where, as long as the outlet (control) pressure is above its set point, the pilot valve plug or disk remains closed. The main spring force, combined with inlet pressure bleeding through the restrictor, provides downward loading pressure to keep the main valve diaphragm and plug assembly tightly shut off. When the outlet pressure drops below the pilot's set point, the pilot plug or disk assembly opens, allowing loading pressure to bleed downstream faster than it can be replaced through the supply line. This reduction in loading pressure on top of the main valve diaphragm and plug assembly allows the unbalanced force between inlet and loading pressure to overcome the main spring force, opening the Type LR125 diaphragm and plug assembly. As the outlet pressure rises back towards the set point, it compresses the pilot diaphragm against the pilot control spring, closing the pilot valve plug or disk. Loading pressure then builds on the Type LR125 diaphragm and plug assembly, pushing it onto the tapered-edge seat for tight shutoff.

The Type MR95H pilot is a pressure-reducing pilot for outlet pressures ranging from 15 to 150 psig (1.0 to 10.3 bar) and handles inlet pressures up to 300 psig (20.7 bar). The Type MR95HP pilot is a pressure-reducing pilot for outlet pressures from 15 to 400 psig (1.0 to 27.6 bar) and handles inlet pressures up to 600 psig (41.4 bar).

The Type LR125 is designed for liquid service and should not be operated in applications where temperatures are below the process fluid's freezing point or above its boiling point, as these limits are dependent on the process fluid and application pressures.

Important Technical Specifications

  • Main Valve Body Sizes: Available in 1, 2, 3, and 4 inch (DN 25, 50, 80, and 100).
  • End Connection Styles: NPT, SWE, CL150 RF, CL300 RF, CL600 RF, and PN 16/25/40 RF.
  • Main Valve Body Material: WCC Steel, CF8M Stainless Steel, CF3M Stainless Steel.
  • Maximum Operating Inlet Pressures:
    • WCC Steel: Up to 600 psig (41.4 bar) for NPT/SWE, CL150 RF, CL600 RF, and PN 16/25/40 RF. Up to 750 psig (51.7 bar) for CL300 RF.
    • CF8M Stainless Steel: Up to 550 psig (37.9 bar) for NPT, CL600 RF, and PN 16/25/40 RF. Up to 275 psig (19.0 bar) for CL150 RF. Up to 720 psig (49.6 bar) for CL300 RF.
  • Outlet (Control) Pressure Ranges:
    • Type MR95H: 15 to 30 psig (1.0 to 2.1 bar), 25 to 75 psig (1.7 to 5.2 bar), 70 to 150 psig (4.8 to 10.3 bar).
    • Type MR95HP: 15 to 100 psig (1.0 to 6.9 bar), 80 to 400 psig (5.5 to 27.6 bar).
  • Main Valve Plug Travel: Ranges from 0.37 in. (9.4 mm) for 1 in. / DN 25 to 1.19 in. (30 mm) for 4 in. / DN 100.
  • Main Valve Internal Inlet Strainer Sizes: 12 Mesh (0.0661 in. / 1.68 mm) for 1 in. / DN 25, and 10 Mesh (0.0787 in. / 2 mm) for 2, 3, and 4 in. / DN 50, 80, and 100.
  • Diaphragm Materials: 17E68 Nitrile (NBR) (Standard), 17E97 Nitrile (NBR) (High erosion resistance), 17E88 Fluorocarbon (FKM) (High temperature capability).
  • Pilot: Type MR95H/MR95HP, 1/2 NPT body size.
  • Restrictor: Type 112, 15-5 Stainless steel body.

Usage Features

  • Installation Flexibility: The robust design allows for indoor or outdoor installation. The regulator can be installed in any orientation as long as flow matches the arrow on the main valve body and the pilot vent is pointed down. For easier maintenance, installation with the bonnet up is recommended.
  • Pilot Vent Orientation: When installed outdoors, the Type MR95H/MR95HP pilot should be oriented so that the spring case vent points down to prevent accumulation of rain, moisture, insects, or debris.
  • Control Line Connection: A downstream pressure control line (minimum 1/2 in. / 13 mm) should be connected to the pilot control line or outlet connection, at least 8 to 10 pipe diameters downstream of the regulator in a straight run of pipe, avoiding turbulent areas.
  • Restrictor Adjustment: The Type 112 restrictor controls the regulator's accuracy and speed of response. A setting of "4" is recommended for optimal accuracy, speed of response, and stability. Lower settings provide tighter control (increased opening speed, decreased closing speed), while higher settings provide maximum stability (decreased opening speed, increased closing speed). The "8" position offers the largest flow, most stability, and easiest startup.
  • Travel Indicator (Optional): Provides a visual indication of the main valve's position.

Maintenance Features

  • Periodic Inspection: Regulator parts are subject to normal wear and must be inspected periodically and replaced as necessary. The frequency of inspection depends on service conditions, applicable codes, and company procedures.
  • Diaphragm and Plug Assembly Maintenance: The diaphragm and plug assembly can be replaced as a single unit or individual components. Instructions are provided for disassembly and reassembly, including specific torque values for components.
  • Travel Indicator Assembly Maintenance: The travel indicator assembly can be removed and installed without removing the bonnet. Maintenance involves checking for damaged or worn parts and replacing them as needed.
  • Type 112 Restrictor Maintenance: Regular inspection and cleaning of the restrictor are recommended to ensure optimum performance, as mineral deposits, dirt, or sediment can clog it, slowing unit response. Instructions are provided for disassembly, inspection, and cleaning of the restrictor.
  • Strainer Maintenance: The internal inlet strainer prevents large particles from entering the main valve. If continuous particles are present in the flowing media, upstream filtration is recommended, and the strainer should be regularly inspected and cleaned.
  • Lubrication: When lubrication is required, a good quality lubricant should be lightly coated on recommended parts. Specific lubricants (Lithium Polymer Type Lubricant, Anti-Seize Lubricant) are specified for various components.
  • Troubleshooting Guide: A comprehensive guide is provided to address common issues such as outlet pressure fluctuations, fluid leaks, and regulator opening/closing problems, with suggested solutions.