Type LR125
9
!
WARNING
!
WARNING
Type 112 Restrictor Adjustment (Figure 5)
The Type 112 restrictor controls the regulator’s 
accuracy and speed of response. A restrictor setting 
of 4 is recommended to optimize accuracy, speed 
of response and stability. However, the restrictor 
can be used to ne tune the regulator for maximum 
performance by decreasing the restrictor setting for 
tighter control (increased opening speed, decreased 
closing speed); or increasing the restrictor setting 
for maximum stability (decreased opening speed, 
increased closing speed). A lower setting also provides 
a narrower proportional band for better accuracy. The 
“8” position has the largest ow, is most stable and 
easiest for startup, however, using the “8” position 
is not necessary. The “0” setting has the smallest 
(minimum) ow passage; at no point of rotation will the 
Type 112 restrictor be completely shut o. After initial 
adjustment, the restrictor does not need to be adjusted 
for maintenance or startup.
Note
Mineral, dirt and sediments may gradually 
deposit and build up inside the spaces 
of the restrictor. This may cause the 
unit response to get slower and unit 
performance to decrease. If clogging of the 
restrictor is suspected, immediately check 
and clean the restrictor. Regular inspection 
of the restrictor is recommended to 
ensure optimum performance. Refer to the 
Type 112 Restrictor Maintenance section. 
Likewise, debris in the process uid 
may clog the restrictor. Install strainer 
upstream of the regulator to prevent 
debris from clogging the restrictor. 
Regular inspection, maintenance and 
cleaning of the strainer is recommended 
to ensure optimum performance.
Recommended Type 112 Restrictor 
Setting Guide (Figure 5)
This guide can be used to adjust performance 
according to application conditions. The recommended 
initial setting is 4.
Shutdown
If pilot supply pressure is shut down 
rst, the downstream system may be 
subjected to full inlet pressure.
1.  If the pilot setting must be disturbed, be sure to 
keep some tension on the spring. This will prevent 
trapping inlet pressure during blow down.
2.  Close the valves shown in Figure 3, in the 
following order: 
a. Inlet block valve
b. Outlet block valve
c. Control line valve(s), if used
3.  Open the vent valves to depressurize the system.
Maintenance
Regulator parts are subject to normal wear and 
must be inspected periodically and replaced as 
necessary. Due to the care Emerson takes in meeting 
all manufacturing requirements (heat treating, 
dimensional tolerances, etc.), use only replacement 
parts manufactured or furnished by Emerson. Also, 
when lubrication is required, use a good quality 
lubricant and lightly coat the recommended part. 
The frequency of inspection and parts replacement 
depends upon the severity of service conditions, 
applicable codes and government regulations and 
company inspection procedures. Table 8 lists possible 
regulator issues and solutions for them.
Type LR125 Main Valve Trim Parts
Instructions are given for complete disassembly and 
assembly. The main valve may remain in the pipeline 
during maintenance procedures. Key numbers are 
referenced in Figures 10 through 14.
Avoid personal injury or damage 
to property from sudden release of 
pressure or uncontrolled process uid. 
Before starting to disassemble, carefully 
release all pressures according to the 
Shutdown procedure. Use gauges to 
monitor inlet and outlet pressures while 
releasing these pressures.
Disassembly
Disassembly of Type LR125:
1.  Shutdown, isolate and depressurize the main valve 
and pilot according to the shutdown procedure.
2.  Remove the cap screws (key 3). Lift up and 
remove the bonnet (key 2) from the body (key 1).