Quick Start Guide Section 1
GFK-2941K Sep 2019
User Features 6
1.2. Light-Emitting Diode Indicators (LEDs)
Status Indicators
LED
LED State
Operating State
CPU OK
On Green
CPU has passed its power-up diagnostics and is
functioning properly. (After initialization sequence
is complete.)
Off
Power is not applied, or CPU has a problem,
which may be indicated by blink pattern.
Blinking
Other
LEDs off
CPU in Stop-Halt state; possible watchdog timer
fault. If the programmer cannot connect, cycle
power with charged Energy Pack attached and
refer to fault tables.
CPU OK
On Amber
CPU indicating CPU320/CRU320 compatibility
setting
FORCE
On Amber
Refer to the section, Backward Compatibility with
CPU320/CRU320/CPU315 for more information.
RUN
Blinking in
unison
CPU is updating an internal programmable
hardware device.
OUT EN
RUN
On Green
CPU is in Run mode.
Off
CPU is in Stop mode.
OUT EN
On Green
Output scan is enabled.
Off
Output scan is disabled.
FORCE
On Amber
Override is active on a bit reference.

Other manuals for Emerson IC695PNC001-BFBE1 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson IC695PNC001-BFBE1 2 and is the answer not in the manual?

Emerson IC695PNC001-BFBE1 2 Specifications

General IconGeneral
BrandEmerson
ModelIC695PNC001-BFBE1 2
CategoryController
LanguageEnglish

Related product manuals