Chapter 11 Specifications 37
Parameters
Product model
GXT4-5000RT230
GXT4-5000RT230E
4000W/5000VA
GXT4-6000RT230
GXT4-6000RT230E
4800W/6000VA
GXT4-10000RT230
GXT4-10000RT230E
9000W/10000VA
Agency
Safety
IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC
IEC/EN/AS 62040-2 2nd Ed (Cat 2 Table 6)
ESD
IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility
IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient
IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity
IEC/EN EN61000-4-5, Level 3, Criteria A
Transportation
ISTA Procedure 1A&E
Table 11-2 Operating temperature parameters
Ambient Temperature, °C (°F)
pf @30°C ± 3°C (pf @ 86°F ± 5.4°F)
pf @40°C ± 3°C (pf @ 104°F ± 5.4°F)
GXT4-5000/6000RT230
GXT4-5000/6000RT230E
0.8pf 0.8pf
GXT3-10000RT230
GXT3-10000RT230E
0.9pf 0.8pf
Table 11-3 Power distribution specifications
Model Number
PD2-CE6HDWRMBS
PD2-CE10HDWRMBS
Amp Rating
32 Amps
63 Amps
Input Power Connection
Single-phase (L-N-G) hard-wired, 6mm
2
~ 10mm
2
(8 ~ 10AWG)
Output Power Connection
Single-phase (L-N-G) hard-wired, 6mm
2
~ 10mm
2
(8 ~ 10AWG)
Includes:
Two IEC320 C19 16A/250V Sockets
Six C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Four IEC320 C19 16A/250V Sockets,
Four C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit
Breaker, Supplied by User
32A 63A
Table 11-4 External battery cabinet specifications
Parameter
Model Number
GXT4-240VBATT
GXT4-240VBATTE
Used UPS model
GXT4-5000RT230
GXT4-6000RT230
GXT4-10000RT230
GXT4-5000RT230E
GXT4-6000RT230E
GXT4-10000RT230E
Dimensions, Rack Mount, W × D × H, mm (in)
Unit
430 × 581 × 173 (16.9 × 22.9 × 6.8)
Shipping
530 × 745 × 475 (20.9 × 29.3 × 18.7)
Weight, kg (lb)
Unit
65 (143.3)
Shipping
79.8 (175.6)
76 (167.6)
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity × V × Rating
20 × 12V × 9.0 AH
Battery Mfr / Part #
CSB/HR12460
Backup Time
See Table 11-5
Environmental
Operating Temp, °C (°F)
0 to 40 (32 to 104);see Table 11-2
Storage Temp, °C (°F)
-15 to 50 (5 to 122)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 1000m (3280.83 ft.) at 25°C (7F)
Agency
Safety
IEC62040-1:2008 version
Transportation
ISTA Procedure 1E
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual