36 Chapter 11 Specifications
Chapter 11 Specifications
Table 11-1 UPS specifications
Parameters
Product model
GXT4-5000RT230
GXT4-5000RT230E
4000W/5000VA
GXT4-6000RT230
GXT4-6000RT230E
4800W/6000VA
GXT4-10000RT230
GXT4-10000RT230E
9000W/10000VA
Dimensions, Rack Mount, W x D x H
Unit, mm (in)
430 × 574 × 217 (16.9 × 22.4 × 8.5)
430 × 581 × 261 (16.9 × 22.9 × 10.3)
Shipping, mm (in)
516 × 745 × 530 (20.3 × 29.3 × 20.9)
530 × 745 × 563 (20.9 × 29.3 × 22.2)
Weight, kg (lb)
Unit, kg (lb)
60 (132.2)
70 (154.3)
Shipping, kg (lb)
Input AC Parameters
Nominal Operating
Frequency
50Hz or 60Hz (Factory Default is 50Hz)
Factory Default VAC
230Vac
User Configurable VAC
220/230/240Vac
(May be modified using included configuration program)
Operating Voltage Range
Without Battery Operation
176Vac ~ 280Vac
Input Frequency w/o Battery
Operation
40Hz ~ 70Hz
Maximum Allowable VAC
280Vac
Input Power Connection
PD2-CE6HDWRMBS Standard
(See 3.2 Removable Power Distribution Box)
PD2-CE10HDWRMBS Standard
(See 3.3 Removable Power
Distribution Box)
Output AC Parameters
Factory Default VAC
230Vac
AC-AC Efficiency
92% AC-AC
Output Connections
PD2-CE6HDWRMBS Standard
(See 3.2 Removable Power Distribution Box)
PD2-CE10HDWRMBS Standard
(See 3.2 Removable Power
Distribution Box)
Frequency
50Hz or 60Hz, Nominal
Waveform
Sinewave
Main Mode Overload
>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute
Internal Battery Charger
Charger Current
1.3
2.6
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity × V
20 × 12V
Battery Mfr. / Part # 5AH battery, CSB HR1221W or YUASA NPH5-12
9AH battery, CSB HR1234W
or Panasonic UP-RW1245
Backup Time
See Table 11-5
Recharge Time (Internal
Batteries)
3 hr. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass Operation
If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation
If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation
When the input frequency prevents synchronous operation
Environmental
Operating Temp, °C (°F)
0 to 40 (32 to 104)see Table 11-2
Storage Temp, °C (°F)
-15 to 50 (5 to 122)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise less than <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual