Table 8-3 Backup time list 1
Backup time
No. of the
battery module
18kW 14.4kW 13.5kW 10.8kW 9kW 7.2kW
4 5m 8m 9m 13m 16m 25m
6 10m 15m 16m 25m 30m 45m
8 17m 25m 27m 35m 50m 1h
10 25m 33m 38m 50m 1h 1h30m
Table 8-4 Backup time list 2
Backup time
No. of the
battery module
5.4kW 4.5kW 3.6kW 3kW 1.8kW 1.5kW
4 38m 50m 1h 1h25m 2h30m 3h
6 1h 1h25m 1h48m 2h10m 4h 4h53m
8 1h36m 1h54m 2h30m 3h 5h40m 7h
10 2h 2h30m 3h10m 4h 7h17m 8h21m
For U16-09C1 battery module, when it is at full load (18kW), the backup time of four battery modules is about six
minutes, and backup time of ten battery modules is about 30 minutes. When it is at half load (9kW), the backup time
of four battery modules is about 20 minutes, and backup time of ten battery modules is about 75 minutes. See Table
8-5 and Table 8-6 for details.
Table 8-5 Backup time list 3
Backup time
No. of the
battery module
18kW 14.4kW 13.5kW 10.8kW 9kW 7.2kW
4 6m 10m 11m 16m 20m 31m
6 12m 18m 20m 31m 37m 56m
8 21m 31m 33m 43m 62m 1h15m
10 31m 41m 47m 62m 1h15m 1h52m
Table 8-6 Backup time list 4
Backup time
No. of the
battery module
5.4kW 4.5kW 3.6kW 3kW 1.8kW 1.5kW
4 47m 62m 1h15m 1h46m 3h07m 3h45m
6 1h15m 1h46m 2h15m 2h42m 5h 6h06m
8 2h 2h22m 3h07m 3h45m 7h05m 7h35m
10 2h30m 3h07m 3h57m 5h 9h06m 10h26m
Note
The backup time will have some difference owing to the different battery manufacturer, model and using time. The data in above
table is only for reference.
8.3 POD
POD (option of the UPS) can provide safe and reliable power distribution function. The descriptions of the POD are
listed in Table 8-7.
Table 8-7 POD
Type Name Description
UF-POD3U20K10 Single POD Dimension (Height × Width × Depth): 435mm × 130mm × 500mm; Weight: 17kg
UF-POD6U20K11 1 + 1 parallel POD Dimension (Height × Width × Depth): 435mm × 260mm × 500mm; Weight: 25kg
For the installation and commissioning of the POD, refer to Liebert
®
ITA 16kVA And 20kVA UPS Power Output
Distribution Unit User Manual.
Remove the plastic panel to reveal the POD front panel; remove the rear baffle plate to reveal the POD rear panel.
The front panel and rear panel of the single POD are shown in Figure 8-4. The front panel and rear panel of the 1 + 1
parallel POD are shown in Figure 8-5.