Options
82
10.1.4 Communication and Monitoring
Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for
connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status
information and all measured parameters for display through a Web browser.
Table 21 Liebert NX communication options
Physical
description
of port
Labeled
ID Name
of Port
On the UPS
LCD screen,
under Settings,
controlled by:
Monitoring
Devices
supported
Baud
rate Comments
Top
Liebert
IntelliSlot
Intellislot 2
(On Monitor
Board)
Comm 1
Multiport 4 any
Relaycard-int any
Liebert IntelliSlot
WEB-LB
2400
Not simultaneous with
Multilink in RS232-1;
See 10.1.5 - Configuring
Baud Rates
Modbus/Jbus
2400
See 10.1.5 - Configuring
Baud Rates
Middle
Liebert
IntelliSlot
Intellislot 1
(On Monitor
Board)
Comm 2
Multiport 4 any
Relaycard-int any
Liebert IntelliSlot
WEB-LB
2400
See 10.1.5 - Configuring
Baud Rates
Not simultaneous with
Multilink in RS232-2
Modbus/Jbus
2400
See 10.1.5 - Configuring
Baud Rates
Bottom
Liebert
IntelliSlot
Intellislot 3
(On Monitor
Board)
Comm 3
Multiport 4 any
Relaycard-int any
Liebert IntelliSlot
WEB-LB
2400
See 10.1.5 - Configuring
Baud Rates
Modbus/Jbus
2400
See 10.1.5 - Configuring
Baud Rates
Top
DB9 port
RS232-1 Comm 1
MultiLink Serial
9600
Not simultaneous with Web
card in top Liebert
IntelliSlot.
Bottom
DB9 port
RS232-2 Comm 2
Service Software
(Reserved) 9600
Not simultaneous with Web
card in middle Liebert
IntelliSlot.