91
Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
2/0 10 N*m
Main Input
(Dual Input)
2/0 10 N*m
Bypass Input
(Dual Input)
1/0 10 N*m
Output 1/0 10 N*m
Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
4/0 10 N*m
Main Input
(Dual Input)
4/0 10 N*m
Bypass Input
(Dual Input)
2/0 10 N*m
Output 2/0 10 N*m
Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
250 10 N*m
Main Input
(Dual Input)
250 10 N*m
Bypass Input
(Dual Input)
4/0 10 N*m
Output 4/0 10 N*m