EasyManuals Logo

Emerson Liebert NX User Manual

Emerson Liebert NX
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Single Module UPS Installation
13
Figure 4 Jumper connection for BCB interface
1.8.4 Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6). The relay con-
tacts are suitable for extra-low voltage applications up to 1A.
Figure 5 Output dry contacts and EPO wiring
Table 6 Output dry contact relays
Position
Name
Description
J13.2 BFP_O Bypass feedback protection relay; normally open; closed when bypass SCR is shorted
J13.3 BFP_S Bypass feedback protection relay center
J13.4 BFP_C Bypass feedback protection relay; normally closed; open when bypass SCR is shorted
J21.2 INV_O Inverter mode relay; normally open; closed when UPS is in inverter mode
J21.3 INV_S Inverter mode relay center
J21.4 INV_C Inverter mode relay; normally closed. Opened when UPS is in inverter mode
J25.2 ACF_O Main input fault relay; normally open. Closed when main input is in fault
J25.3 ACF_S Main input fault relay center
J25.4 ACF_C Main input fault relay; normally closed. Open when main input is in fault
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
UPS Monitoring Board
J10
OL
DRV
GND
FB
Battery Circuit Breaker
OL
Aux – N.O.
Aux – N.O.
EPO - NCEPO - NO
X2X1
BFP_C
J21 J25 J28
BFP_S
BFP_O
INV_O
INV_S
INV_C
ACF_C
ACF_S
ACF_O
J13
+12V

Table of Contents

Other manuals for Emerson Liebert NX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Liebert NX and is the answer not in the manual?

Emerson Liebert NX Specifications

General IconGeneral
BrandEmerson
ModelLiebert NX
CategoryUPS
LanguageEnglish

Related product manuals