REV. 5 7/6/2007
Liebert Monitoring Group –Development
17
Ambient Temperature
Warning Point 30069 40069 1 1 deg C
Over Temperature Limit
Point 30072 40072 1 1 deg C
Load (Apparent Power)
30102 2 1 VA
Load (Real Power)
30104 2 1 W
Load / Capacity
30106 1 1 %
Input Frequency
30107 1 10 Hz
Output Frequency
30108 1 10 Hz
Battery Charge Status
30112 1
1 - 100% Charged
2 - Less than 100%
Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113 1 1 V
Battery Time Remaining
30115 1 1 min
Battery Charge
Percentage
30116 1 1 %
Ambient Temperature
30119 1 1 deg C
Battery Test Result
30130 1 1
Input Voltage L1
30153 1 1 V
Input Current L1
30154 1 1 A
Output Voltage L1
30163 1 1 V
Output Current L1
30164 1 1 A
Input Maximum Voltage
L1
30180 1 1 V
Input Minimum Voltage
L1
30181 1 1 V
Output Maximum
Voltage L1
30182 1 1 V
Output Minimum
Voltage L1
30183 1 1 V
Black Out Count
30301 1 1
Brown Out Count
30302 1 1