REV. 5 7/6/2007
Liebert Monitoring Group –Development
6
Battery Charge Percentage 30116 1 1 %
Battery Temperature 30117 1 1 deg C
Transformer Temperature 30121 1 1 deg C
Redundant Power Modules 30124 1 1
Active Power Module Count 30126 1 1
Battery Module Active
Count 30127 1 1
Battery Test Result 30130 1 1
Input Voltage L1 30153 1 1 V
Input Current L1 30154 1 1 A
Bypass Voltage L1 30159 1 1 V
Bypass Current L1 30160 1 1 A
Output Voltage L1 30163 1 1 V
Output Current L1 30164 1 1 A
Power Module Failure
Count 30304 1 1
Battery Module Failure
Count 30305 1 1
Power Module Warning
Count
30306 1 1
Battery Module Warning
Count
30307 1 1