Document Part # 026-4176 Rev 1 Page 14 of 16
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
12.From the Details screen, click Commands on the far right and select DRIVE-RESET. The drive is
now reset with the needed configuration.
STEP 6: Verification of Settings
1. After commissioning the new device, verify that the following values are set in the drive:
0.009 (MOTOR_PWR_FACTOR) = 0.85 or the value that you set
6.004 (Start/Stop Logic) = 6
8.023 (Digital input 3) = 0.000
The following parameters must be set up in the Inputs tab to run the drive.
RUN (ON)
DIRECTION (FORWARD, REVERSE)
REF FREQ (the speed setting of the motor)
Figure 18 - Application Commands - DRIVE-RESET