EasyManua.ls Logo

Emerson M400 - Page 15

Emerson M400
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Document Part # 026-4176 Rev 1 Page 15 of 16
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
2. Use Table 1- Menu 0 Guide to verify values set in the M400 drive.
Note: Table 1- Menu 0 Guide gives diagnostic information about the system. It allows you to double check
to make sure that the E2 controller sent the correct parameters.
Menu 0 Pr Description Value to Write Comments Parameter Type
1 Drive Configuration Preset Sets drive mode to Preset 11.034 Mode
2 Serial Baud Rate 19200 Sets baud to 19200 11.025 Mode
3 Serial Address 2 Set the address for each drive on network. 11.023 Mode
4 Serial Mode 8 1 NP Set to match mode of E2E 11.024 Mode
5
Reset Serial
Communications
Toggle ON/
Set this to ON / OFF to reset communications.
Connects
11.02 Mode
6 Motor Rated Current See Motor Set from motor nameplate. 5.007 Motor
7 Motor Rated Speed See Motor Set from motor nameplate. 5.008 Motor
8 Motor Rated Voltage See Motor Set from motor nameplate. 5.009 Motor
9 Motor Power Factor See Motor
Set from motor nameplate. (Use 0.85 if
absent.)
5.010 Motor
10
Security / Parameter
Access
Set to All Menus Set to all Menus to see access Menu 1 to 22
11.044
Access
12 STO 1 State RO 0=disabled, 1=enabled 8.039 Info
13 STO 2 State RO 0=disabled, 1=enabled 8.040 Info
Table 1 - Menu 0 Guide
Figure 19 - Setting Up Inputs Tab