5700 ATEX Installation Instructions
December 2015 EB-20025742 Rev. AC
5 of 12
3) Parameters
3.1 Mains circuits:
3.1.1 for type 5700*1*(A,E,N)******(J1, terminal 1 - 2)
voltage AC/DC 18 - 240 V + 10 %
max. voltage Um AC/DC 265 V
3.1.2 for type 5700*1*C******(J6, terminal 1 - 2)
voltage AC/DC 18 - 240 V + 10 %
max. voltage Um AC/DC 265 V
3.2 Non intrinsically safe input/output circuits:
3.2.1 For all types(J2, USB)
voltage Um AC/DC 10 V
3.2.2 for type 5700*1*A******(J3,terminals 1-10)
voltage Um AC/DC 30 V
3.2.3 for type 5700*1*N******(J3,terminals 1-2, FF)
voltage Um DC 33 V
3.2.4 for type 5700*1*N******(J3,terminals 3-4, mA)
voltage Um DC 30 V
3.2.5 for type 5700*1*N******(J3,terminals 5-6, FO/DO)
voltage Um DC 30 V
3.2.6 for type 5700*1*C******(J5,terminals 1-2)
voltage Um AC/DC 30 V
3.2.7 for type 5700*1*C******(J7/J8,ETHERNET RJ-45)
voltage Un DC 2,4 V
3.3 Intrinsically safe circuits “ic”:
3.3.1 for type 5700*1*E******(J3,terminals 1-2 FF)
voltage Ui DC 30 V
current Ii 300 mA
power Pi 1,3 W
effective internal inductance Li 5 μH
effective internal capacitance Ci 0,27 nF