GFK-2573Z Sep 2020
8
Version
Firmware
Revision
Date
Comments
IC695PNC001-AM
2.26
Jun
2016
Supports the Remote Get HART Device Information COMMREQ. Information from a
HART device connected to an RX3i Analog Module in an IC695PNS001 RX3i
PROFINET Scanner may be read into the user application using the Remote Get HART
Device Information COMMREQ.
IC695PNC001-AL
2.25
Nov
2015
Supports extended PROFINET device Subslot Numbers in order to support additional
3rd party devices. The maximum Subslot Number has been increased from 255 to
21845.
IC695PNC001-AK
2.20
May
2015
Added support for HART
®
Pass Through feature set over PROFINET. A HART capable
PROFINET scanner (IC695PNS001 or IC695CEP001) must also be employed to
support the HART capable RX3i analog modules over PROFINET. The CPU used in the
application must also contain firmware which supports HART Pass Through.
IC695PNC001-AJ
2.11
Feb
2015
Increased number of PROFINET Devices that PNC001 can control from 64 to 128.
Still limited to 63 devices in an MRP Ring if the PNC001 is the MRP Ring Manager.
Added new SFP OK status bits to existing PNC001 status dword.
Introduced new Critical Network Port diagnostic fault configuration and logging.
Configuring ports as critical also forces Copper ports to 100 Mbps.
IC695PNC001-AH
2.05
Jun
2014
Adds support for COMMREQs required by the Genius Communication Gateway
(GCG001) module.
IC695PNC001-AG
2.00
Dec
2013
Adds remote PROFINET IO to PACSystems RX3i Hot Standby Redundancy systems.
Also adds MRP status bits.
For details, see New Features and Enhancements below.
IC695PNC001-AF
1.23
Aug
2013
Corrects issue storing PROFINET device configuration greater than 64K bytes in size.
For details, see RX3i PROFINET Controller IPI, GFK-2573F.
IC695PNC001-AE
1.22
Jul
2013
Corrects an issue where, in some configurations, the PNC001 entered a mode that
caused it to repeatedly power up.
IC695PNC001-AD
1.21
Jul
2012
Addresses a power-up issue affecting the following revisions IC695PNC001-AB and
IC695PNC001-AC.
Although no units that exhibited this issue were shipped, it is recommended to
update firmware to prevent the possibility of encountering a power up issue in the
field.
IC695PNC001-AC
1.20
Mar
2012
Adds support for up to 255 PROFINET IO Devices per RX3i CPU.
IC695PNC001-AB
1.10
Dec
2011
Adds support for SNMP and LLDP standards to facilitate network management.
Provides enhanced Revision Information in the Explore PROFINET Networks tool.
IC695PNC001-AA
1.00
Jun
2011
Initial release.
Supports GSDML Version 2.2 and earlier.
HART
®
is a registered trademark of the HART Communication Foundation of Austin, Texas USA. Any use of the term HART hereafter in this document, or any
document referenced by this document, implies the registered trademark.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson PACSystems RX3i PROFINET and is the answer not in the manual?

Emerson PACSystems RX3i PROFINET Specifications

General IconGeneral
BrandEmerson
ModelPACSystems RX3i PROFINET
CategoryController
LanguageEnglish

Related product manuals