GFK-2573Z Sep 2020
4
ATEX Zone 2
This module must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC
and rated IP54. The enclosure shall only be able to be opened with the use of a tool.
Status Reporting
The PNC001 provides 32 bits of status information to a configured location in the RX3i CPU’s reference memory.
The status data consists of the Module OK bit, which indicates the health of the module itself, a status bit for each
external port, and a bit that indicates the connection status of the configured devices.
All Status bits are active high. The status location may be configured in %I, %Q, %AI, %AQ, %R, %G, %T, %M or %W or I/O
Variable reference memory in the RX3i CPU.
Status Bit Definitions
Name
Description
Module OK
Indicates the health of the PNC001 module.
1 indicates the module is functioning properly.
0 indicates the module is powering up or has failed.
Port1 Link Up
1 indicates the port is connected to another device and is operating correctly.
0 indicates the port is not connected to another device or the port has an error preventing
communications, or the SFP cage is empty or has an incompatible SFP device.
Port2 Link Up
Port3 Link Up
Port4 Link Up
Reserved
Reserved. Always 0.
Port3 SFP OK
Indicates the health of the SFP plugged in port 3.
1 indicates that the SFP matches configuration and is operational.
0 indicates that either the SFP does not match configuration or is not operational.
Port4 SFP OK
Indicates the health of the SFP plugged in port 4.
1 indicates that the SFP matches configuration and is operational.
0 indicates that either the SFP does not match configuration or is not operational.
All Devices
Connected
3
1 indicates all configured devices are connected and communicating over PROFINET.
0 indicates no devices are configured or one or more configured devices have not established a
PROFINET connection.
10
Reserved
Always 0.
11
MRP Enabled
0 indicates that MRP is not enabled.
1 indicates that MRP is enabled.
12
MRP Role
If MRP is enabled:
0 indicates that the PNC001 is currently an MRP client.
1 indicates that the PNC001 is currently the MRP Manager.
If MRP is not enabled, this bit will be set to 0.
13
MRP Ring Status
If MRP is enabled and the PNC001 is currently the MRM:
0 indicates that the ring is open (ring broken).
1 indicates that the ring is closed (ring complete).
If MRP is not enabled or if the PNC001 is an MRC, this bit will be set to 0.
14-32
Reserved
Set to 0
3
It is recommended that the All Devices Connected status bit be checked first to determine whether all devices belonging to the PNC001 are functioning. If
this bit is 0, indicating that one or more devices is not OK, the PNIO_DEV_COMM function block can then be used to determine which specific devices are
not communicating. For details on this status bit, refer to the section entitled Status Reporting in the RX3i PROFINET I/O Controller Manual, GFK-2571.

Questions and Answers: