4 Connect the wiring and power up
Shielded twisted pair cable should be used for best results. Use 24 AWG or
larger wire that does not exceed 5000 ft. (1500 m) in length. If applicable,
install wiring with a drip loop. Arrange the drip loop so the bottom is lower
than the conduit connections and the transmitter housing.
Figure 4-1: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R
L
≥ 250 (necessary for HART Communication only)
Figure 4-2: Wiring the Transmitter (1–5 Vdc Low Power)
A. Power supply
B. Voltmeter
C. Field terminals
March 2022 Quick Start Guide
Quick Start Guide 11