Manual Supplement
00809-0400-2410, Rev AA
Rosemount 2410 Tank Hub
March 2016
Rosemount 2410 Tank Hub
All Enraf unit types are separately configurable (optional).
5. In the drop-down list for Emulation Units, select desired unit types.
6. Select Apply.
1.4.4 Configure field devices
When the tank hub configuration is completed the Rosemount field devices, for example
Rosemount 5900 Radar Level Gauge and Rosemount 2240S Multi-input Temperature
Transmitter, must be configured as well. The field devices are configured as usual, for
information see the Rosemount Tank Gauging System Configuration manual
(document number 00809-0300-5100).
1. Configure the field devices by using the Properties window of each device.
2. Verify that measured data such as level, temperature etc. are valid.
1.4.5 Connect the CIU
1. When configuration is completed, close TankMaster WinSetup and disconnect the
EBM.
2. Connect the bus to the CIU.
3. The tank hub will now switch to Enraf mode and act like an Enraf gauge.