50
Reference Manual
00809-0100-4825, Rev CB
Section 4: Operation and Maintenance
March 2014
Operation and Maintenance
No simulation devices available. There are no device descriptions available to simulate a device.
No UPLOAD_VARIABLES in ddl for this
device
There is no menu named “upload_variables” defined in the device description for
this device. This menu is required for offline configuration.
No Valid Items The selected menu or edit display contains no valid items.
OFF KEY DISABLED Appears when the user attempts to turn the Field Communicator off before sending
modified data or before completing a method.
Online device disconnected with
unsent data. RETRY or OK to lose
data.
There is unsent data for a previously connected device. Press RETRY to send data, or
press OK to disconnect and lose unsent data.
Out of memory for hotkey
configuration. Delete unnecessary
items.
There is no more memory available to store additional hotkey items. Unnecessary
items should be deleted to make space available.
Overwrite existing configuration
memory
Requests permission to overwrite existing configuration either by a
device-to-memory transfer or by an offline configuration. User answers using the
softkeys.
Press OK. Press the OK softkey. This message usually appears after an error message from the
application or as a result of HART communications.
Restore device value? The edited value that was sent to a device was not properly implemented. Restoring
the device value returns the variable to its original value.
Save data from device to
configuration memory
Prompts user to press SAVE softkey to initiate a device-to-memory transfer.
Saving data to configuration
memory.
Data is being transferred from a device to configuration memory.
Sending data to device. Data is being transferred from configuration memory to a device.
There are write only variables which
have not been edited. Please edit
them.
There are write-only variables which have not been set by the user. These variables
should be set or invalid values may be sent to the device.
There is unsent data. Send it before
shutting off?
Press YES to send unsent data and turn the Field Communicator off. Press NO to
turn the Field Communicator off and lose the unsent data.
Too few data bytes received Command returns fewer data bytes than expected as determined by the device
description.
Transmitter Fault Device returns a command response indicating a fault with the connected device.
Units for <variable label> has
changed. Unit must be sent before
editing, or invalid data will be sent.
The engineering units for this variable have been edited. Send engineering units to
the device before editing this variable.
Unsent data to online device. SEND or
LOSE data
There is unsent data for a previously connected device which must be sent or
thrown away before connecting to another device.
Use up/down arrows to change
contrast. Press DONE when done.
Gives direction to change the contrast of the Field Communicator display.
Value out of range The user-entered value is either not within the range for the given type and size of
variable or not within the min/max specified by the device.
<message> occurred reading/writing
<variable label>
Either a read/write command indicates too few data bytes received, transmitter
fault, invalid response code, invalid response command, invalid reply data field, or
failed pre- or post-read method; or a response code of any class other than SUCCESS
is returned reading a particular variable.
<variable label> has an unknown
value. Unit must be sent before
editing, or invalid data will be sent.
A variable related to this variable has been edited. Send related variable to the
device before editing this variable.
Message Description