Reference Manual
00809-0100-4811, Rev CA
February 2006
A-3
Rosemount 3300 Series
Measuring Performance
Reference accuracy ± 0.2 inch (5 mm) for probes 16.4 ft (5 m).
± 0.1% of measured distance for probes >16.4 ft (5 m).
Repeatability ± 0.04 inch (1 mm).
Ambient Temperature Effect Less than 0.01 % of measured distance per °C.
Update interval 1 per second
Measuring range 16 inch (0.4 m) to 77 ft (23.5 m).
(1) PFA is a fluoropolymer with properties similar to PTFE.
(2) 1 mm PTFE cover.
(3) Final rating may be lower depending on flange and O-ring selection.
(4) For PTFE Covered Probe and Flange (model code 7) max pressure is 232 psig (16 Bar).